IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS
46 www.DaikinApplied.com
Problem Alarms
Problems do not cause compressor shutdown but do limit operation of the chiller.
Table 14: Unit Problem Alarms
Description
OITS Alarm Message
Alarm Reset
Condenser Water Freeze Protect Comp 1
COND PUMP ON - Condenser Pressure Low (Freeze)
Auto-clears
Condenser Water Freeze Protect Comp 2
COND PUMP ON - Condenser Pressure Low (Freeze)
Auto-clears
Low Evaporator Pressure - Inhibit Loading Circuit 1
NO LOAD - Evaporator Pressure Low
Auto-clears
Low Evaporator Pressure - Inhibit Loading Circuit 2
NO LOAD - Evaporator Pressure Low
Auto-clears
Low Evaporator Pressure - Unload Circuit 1
UNLOAD - Evaporator Pressure Low
Auto-clears
Low Evaporator Pressure - Unload Circuit 2
UNLOAD - Evaporator Pressure Low
Auto-clears
Ground Fault Protection 1
COMPR STOP - Ground Fault
Locked off (requires local reset)
Ground Fault Protection 2
COMPR STOP - Ground Fault
Locked off (requires local reset)
Warning Alarms
Warnings only generate a warning message to the operator. Chiller operation is not affected.
Table 15: Unit Warning Alarms
Description
OITS Alarm Message
Alarm Reset
Entering Condenser Water Temperature Sensor Fault
NO ACTION - Condenser EWT Out of Range
Auto-clears
Entering Evaporator Water Temperature Sensor Fault
NO ACTION - Evaporator EWT Out of Range
Auto-clears
Liquid Line Refrigerant Temperature Sensor Fault
NO ACTION - Liquid Line Temp Out of Range
Auto-clears
Leaving Condenser Water Temperature Sensor Fault
NO ACTION - Condenser LWT Out of Range
Auto-clears
Condenser Pump #1 Fault
No Alert shown on OITS panel
No Alarm
Condenser Pump #2 Fault
No Alert shown on OITS panel
No Alarm
High Discharge Temperature Comp 1
No Alert shown on OITS panel
No Alarm
High Discharge Temperature Comp 2
No Alert shown on OITS panel
No Alarm
Entering Evap Temperature Sensor Fault (EWT reset active)
No Alert shown on OITS panel
No Alarm
Chiller Running with Limited Capacity
No Alert shown on OITS panel
No Alarm
Load Balance Valve Fault 1
COMPR WARNING - Flooded Compressor
Operator Cleared Only
Load Balance Valve Fault 2
COMPR WARNING - Flooded Compressor
Operator Cleared Only
Table 16: Compressor Warning Alarms
Description
OITS Alarm Message
Alarm Reset
Repower After Power Loss 1
COMPR STOP - Line Voltage Low
Auto-clears
Repower After Power Loss 2
COMPR STOP - Line Voltage Low
Auto-clears