INSTALLATION
Type B Knockdown: Bolted Construction, Shipped as Parts
Major components/subsystems are removed and shipped on separate skids for a partially-assembled unit.
Figure 7: Partial Disassembly - Representative Illustration
Scope:
•
All associated piping and wiring remain attached, if possible
•
Compressors and vessels receive an inert gas holding
charge
•
All free piping ends are capped
•
Suction and discharge lines have bolt-on flanges and, if
possible, remain attached
•
Unit ships with vessel and/or head insulation, if ordered
•
Refrigerant will not be shipped with the chiller and must be
procured locally
•
Site re-assembly must be supervised or completed by
Daikin Applied service personnel
•
Ideal for retrofit applications where installation access is
narrow or restricted and where refrigerant may be secured
locally