PHySICAL DATA
MAGNITUDE WMT CHILLER
DAIKIN APPLIED
14
Physical Data
Unit Dimensions
Figure 12: Representative WMT Dimensional Drawing
Table 4: WMT Overall Dimensions
Model
1
Heat Exchanger
Dished Waterbox
Heads Length
2
Marine Waterbox
Heads Length
2
Width
Height
3
WMT301AS
E3612/C3012
169 .25 in .
195 .25 in .
86 .3 in .
99 .18 in .
WMT301AS
E3615/C3015
218 .47 in .
245 .72 in .
86 .3 in .
99 .18 in .
WMT301AS
E4212/C3012
169 .25 in .
195 .25 in .
96 .3 in .
102 .8 in .
Notes:
1. Unit configuration may be different than illustrated. Refer to certified drawings for specific configuration/dimensions.
2. Unit length represents 2 pass, 150 psi water box configuration with grooved connections.
3. Unit height represents largest configuration possible but does not include height of removable eye bolt.
Component Weights
Component
Dry Weight
lbs
kg
Compressor
5,318
2412
Compressor
Platform
763
346
Evaporator
8,358
3791
Condenser
8,098
3673
Power Box
1302
591
Economizer
839
381
NOTICE
Drawings, dimensional values, and other information may
change depending on options or configurations selected. Refer
to the as-built submittal drawings provided by a Daikin Applied
sales representative for configuration-specific details.