35
IOM 1297
WWW.DAIKINAPPLIED.COM
OPERATION
Description
Default
Range
PW
Comments
Tandem
Pressure
Ratio Limit
1.7 for
WMT092
2.0 for
WMT106
1-3.5
O
Max pressure
ratio for which a
lead-lag start will be
performed. A higher
pressure ratio will
trigger a tandem
start .
No. of Com-
pressors
1
1 to 2
O
Software
Enable
Enabled
Enabled,
Disabled
O
Table 9: Compressor Setpoints
Description Default
Range
PW
Comments
Demand Limit/Current Limit (% RLA)
Demand
Limit Enable
OFF
ON, OFF
O
ON: Limits % RLA
to a value set by the
Demand Limit analog
input,
where: 4 mA = 100%
RLA
20 mA = Min-
imum Demand Limit
Setpoint
OFF: The Demand
Limit input is ignored.
Maximum
Amps
100%
70 to
100%
O
Inhibits capacity in-
crease above %RLA.
Unloading forced at
5% above value.
Capacity
VFD Output
Amps
Factory
Set
Model De-
pendent
T
Sets the Rated Load
Amps (RLA) per
compressor phase as
given on the chiller
nameplate - Load
Side Phase Data.
Wheel
Wheel Type
Factory
Set
Model De-
pendent
T
Size of compressor
and impeller type
Harmonic Filter
Amp Rating
Factory
Set
Model De-
pendent
T
Based on model of
harmonic filter
CAUTION
Chiller Nameplate RLA
MUST
match chiller dataplate per
compressor.
Figure 37: Settings View - Tower
Table 10: Tower Setpoint Settings
Description
Default
Range
PW
Comments
Tower Bypass
Valve Target
-Temp
65
40 – 120
O
Target value for
entering condenser
water temperature
Valve Target
- Lift
30
10 – 100
O
Target value for lift
pressure
Valve Con-
trol Range
- Min
10
0 – 100%
O
Minimum bypass
valve position
Valve Con-
trol Range
- Max
90
0 – 100%
O
Maximum bypass
valve position
Control
Enable Tow-
er Control
Dis
-
abled
Disabled,
Enabled
O
Cooling
Tower
Control
Temp
None,
Temp, Lift
O
Selects target for
tower bypass and
fan control
Tower Fan
VFD
None
None,
VFD
Stage
0, VFD
Stage 1,
VFD all
stages
O
None: No VFD
Control
VFD Stage 0: VFD
independent of fan
stage outputs
VFD Stage 1: VFD
on stage 1 only
VFD all stages: VFD
on all fan stages
Tower Valve
Type
None
None,
Normally
Closed
(NC),
Normally
Open
(NO),
VFD
O
None: No bypass
valve
NC: Valve is normal-
ly closed to tower
NO: Valve is normal-
ly open to tower
VFD: bypass valve
output controls con-
denser pump VFD