OPERATION
MAGNITUDE WMT CHILLER
DAIKIN APPLIED
38
Table 12:
Offsets Setpoint Settings
Description
Default
Range
PW
Comments
Temperature Offsets
Evap EWT
0 .0
-1.5 to
1 .5
T
Sets the offset for the
sensor listed based upon
jobsite calibrations.
Evap LWT
0 .0
-1.5 to
1 .5
T
Cond EWT
0 .0
-1.5 to
1 .5
T
Cond LWT
0 .0
-1.5 to
1 .5
T
Liquid Line
Temp
0 .0
-1.5 to
1 .5
T
1st Stage
Discharge
0 .0
-1.5 to
1 .5
T
1st Stage
Suction
0 .0
-2 to 2
T
2nd Stage
Discharge
0 .0
-1.5 to
1 .5
T
2nd Stage
Suction
0 .0
-2 to 2
T
Current Temperature
Evap EWT
0 .0
-1.5 to
1 .5
T
Sets the offset for the
sensor listed based upon
jobsite calibrations.
Evap LWT
0 .0
-1.5 to
1 .5
T
Cond EWT
0 .0
-1.5 to
1 .5
T
Cond LWT
0 .0
-1.5 to
1 .5
T
Liquid Line
Temp
0 .0
-1.5 to
1 .5
T
Discharge
Temp
0 .0
-1.5 to
1 .5
T
Suction
Temp
0 .0
-2 to 2
T
Pressure Offsets
Evaporator
0 .0
-2 to 2
T
Sets the offset for the
sensor listed based upon
jobsite calibrations.
Condenser
0 .0
-2 to 2
T
Liquid Line
0 .0
-2 to 2
T
1st Stage
Discharge
0 .0
-2 to 2
T
1st Stage
Suction
0 .0
-2 to 2
T
2nd Stage
Discharge
0 .0
-2 to 2
T
2nd Stage
Suction
0 .0
-2 to 2
T
Figure 42: Settings View - Alarms
ALARMS Setpoint Settings
Description
Default
Range
PW
Comments
Pressure Alarm
Low
Evaporator
Pressure
-6.9 psi
-8 to 10
psi
T
Sets the evapora-
tor pressure value
below which the
compressor is shut
down - may need to
be lowered if glycol is
added to the system.
If Glycol Enabled is
selected, minimum
may be set as low as
-8 psi.
High
Condenser
Pressure
30 psi
25 to 35
psi
T
Sets the condenser
pressure limit
Water Flow
Evaporator
Trip Time
1 sec
0 to 5
sec
T
Freeze Protect
Evaporator
Freeze
Protect
34.0°F
34.0 to
38.0°F
T
Sets the value of
evaporator saturated
temperature below
which the evaporator
pump is forced ON -
occurs when unit is
off and chiller senses
need to provide flow
to address a chiller
limit alarm
Condenser
Freeze
Protect
34.0°F
34.0 to
38.0°F
T
Sets the value of
condenser saturated
temperature below
which the condenser
pump is forced ON -
occurs when unit is
off and chiller senses
need to provide flow
to address a chiller
limit alarm.
Glycol
Glycol en-
abled
Off
Off, On
T
Enables Glycol mode
to allow lower tem-
perature setpoints.