OPERATION
MAGNITUDE WMT CHILLER
DAIKIN APPLIED
44
Controller Inputs & Outputs
As outlined below, inputs and outputs vary between the unit
controller and the compressor controller.
Unit Controller Inputs and Outputs
The following tables list the unit controller inputs and outputs,
both analog and digital, as well as the stepper motor outputs.
Table 17: Unit Controller, Analog Inputs
Description
Wiring
Source
Signal
Sensor
Range
Entering
Evaporator
Water Tem-
perature
Chiller
NTC
Thermistor
10k @
25°C
-40 to
125°C
Leaving Evap-
orator Water
Temperature
Chiller
NTC
Thermistor
10k @
25°C
-40 to
125°C
Entering Con-
denser Water
Temperature
Chiller
NTC
Thermistor
10k @
25°C
-40 to
125°C
Leaving Con-
denser Water
Temperature
Chiller
NTC
Thermistor
10k @
25°C
-40 to
125°C
Liquid Line
Refrigerant
Temperature
Chiller
NTC
Thermistor
10k @
25°C
-40 to
125°C
Liquid Enter-
ing Tempera-
ture
Chiller
NTC
Thermistor
10k @
25°C
-40 to
125°C
Economizer
Temperature
Chiller
NTC
Thermistor
10k @
25°C
-40 to
125°C
Liquid Enter-
ing Pressure
Chiller
Sealed
Gage
Transducer
0.5 to
4 .5 VDC
nominal
-14.5 to
21.76 psi
Evaporator
Refrigerant
Pressure
Chiller
Sealed
Gage
Transducer
0.5 to
4 .5 VDC
nominal
-14.5 to
21.76 psi
Liquid Line
Refrigerant
Pressure
Chiller
Sealed
Gage
Transducer
0.5 to
4 .5 VDC
nominal
-14.5 to
21.76 psi
Condenser
Refrigerant
Pressure
Chiller
Sealed
Gage
Transducer
0.5 to
4 .5 VDC
nominal
-14.5 to
21.76 psi
Economizer
Pressure
Chiller
Sealed
Gage
Transducer
0.5 to
4 .5 VDC
nominal
-14.5 to
21.76 psi
EXV Driver
Feedback
Chiller
EXV actu-
ator
4 to 20 mA
Current
0 to 100%
Economizer
Level
Chiller
Level
Sensor
4 to 20 mA
Current
0 to 100%
Reset of
Leaving Water
Temperature
Field
BAS
4 to 20 mA
Current
0 to 100%
Demand Limit
Field
BAS
4 to 20 mA
Current
0 to 100%
NOTICE
“Sensor Range” in
indicates the range of the input, NOT
the operating range of the chiller.
Table 18: Unit Controller, Digital Inputs
Description
Wiring
Signal Source
States (Open/
Closed)
Front Panel
“Stop/Auto”
Switch
Chiller
Isolated Switch
Contacts
Stop/Auto
Remote Start/
Stop
Field
Isolated Switch
or Relay Con-
tacts
Stop/Auto
Evaporator Wa-
ter Flow Switch
Chiller &
Field
(in series)
Isolated Flow
Switch Con-
tacts
No Flow/Flow
Condenser Wa-
ter Flow Switch
Chiller &
Field
(in series)
Isolated Flow
Switch Con-
tacts
No Flow/Flow
Table 19: Unit Controller, Analog Outputs
Description
Output Signal
Sensor Range
EXV Driver Signal
0 to 10 VDC
0 to 100% Open
Cooling Tower Bypass
Valve Position
0 to 10 VDC
0 to 100% Open
Cooling Tower VFD
Speed
0 to 10 VDC
0 to 100%
NOTE:
“Sensor Range” in
Table 28
indicates the range of the
output, NOT the operating range of the chiller.
Table 20: Unit Controller, Digital Outputs
Description
Load
Rating
Alarm
Indicator Light
240 VAC
Evaporator Water Pump #1
Pump Contactor
240 VAC
Evaporator Water Pump #2
Pump Contactor
240 VAC
Condenser Water Pump #1
Pump Contactor
240 VAC
Condenser Water Pump #2
Pump Contactor
240 VAC
Cooling Tower Fan #1
Fan Contactor
240 VAC
Cooling Tower Fan #2
Fan Contactor
240 VAC