OPERATION
Compressor Controller Inputs and
Outputs
The following tables list, for each compressor controller, analog
inputs and digital outputs as well as the stepper motor outputs.
Table 21: Compressor Controller, Analog Inputs
#
Description
Source
Signal
Sensor
Range
1
1st Stage
Suction Pres-
sure
NTC Thermistor
10k @
25°C
-14.5 to
21.76°C
2
1st Stage
Discharge
Pressure
NTC Thermistor
10k @
25°C
-14.5 to
21.76°C
3
2nd Stage
Suction Pres-
sure
NTC Thermistor
10k @
25°C
-14.5 to
43.51°C
4
2nd Stage
Discharge
Pressure
NTC Thermistor
10k @
25°C
-14.5 to
43.51°C
5
Inlet Guide
Vane Posi-
tion
Rotary Trans-
ducer
1.5 to
2 .6 VDC
nominal
Closed to
Open
6
Motor Wind-
ing Tempera-
ture 1
NTC Thermistor
10k @
25°C
-40 to 150°C
7
Motor Wind-
ing Tempera-
ture 2
NTC Thermistor 10k @
25°C
-40 to 150°C
8
Motor Wind-
ing Tempera-
ture 3
NTC Thermistor
10k @
25°C
-40 to 150°C
9
Motor Wind-
ing Tempera-
ture 4
NTC Thermistor
10k @
25°C
-40 to 150°C
10
Motor Wind-
ing Tempera-
ture 5
NTC Thermistor
10k @
25°C
-40 to 150°C
11
Motor Wind-
ing Tempera-
ture 6
NTC Thermistor
10k @
25°C
-40 to 150°C
Table 22: Compressor Controller, Digital Outputs
#
Description
Load
Output
OFF
Output ON
1
VFD Enable
VFD
Compres-
sor OFF
Compressor
ON
Table 23: Compressor Controller, Analog Outputs
Description
Output Signal
Sensor Range
Inlet Guide Vane Driver
Position
0 to 10 VDC
0 to 100%
Building Automation Systems
Daikin Applied unit controllers strictly conform to the
interoperability guidelines of the LonMark Interoperability
Association and BACnet International. They have received
LonMark certification with optional LonWorks communication
module.
Protocol Options
The following protocol options are available:
•
BACnet MS/TP
• BACnet IP
•
LonWorks
•
Modbus RTU
The BAS communication module can be ordered with the chiller
and factory-mounted or can be field-mounted at any time after
the chiller unit is installed. Connection to the chiller for all BAS
protocols will be at the unit controller. An interface card or
module, depending on the protocol being used, will have been
factory installed in the unit controller if so ordered, or it can be
field installed.
If an interface module was ordered, the appropriate BAS
interface installation manual was shipped with the unit. If
necessary, contact your local Daikin Applied sales office for a
replacement manual or obtain one from