IOM 1210-7 • MAGNITUDE
®
MODEL WMC CHILLERS
10 www.DaikinApplied.com
I
nsTallaTIon
Type B Knockdown, “Partial Disassembly”
Compressor(s), power box, and control box are removed and shipped on separate skids; combined vessel stack is shipped
together as a sub-assembly.
Figure 9: Type B Knockdown
Type B Scope:
• Compressor(s), power box, control box and optional
economizer are removed (at the factory) and shipped on
separate skids; vessel stack is shipped as a complete
sub-assembly.
• All associated piping and wiring remain attached, if
possible.
• Suction and discharge lines have bolt-on flanges and, if
possible, remain attached.
• All free piping ends are capped.
• Unit ships with vessel and/or head insulation, if ordered.
• Refrigerant will not be shipped with the chiller and must
be procured by others.
• Compressor(s) and vessels receive an inert gas holding
charge.
• Unit ships with replacement refrigerant gaskets and
O-rings, stick-on wire ties, and touch-up paint.
• Unit is fully tested at the factory prior to shipment.
• Site reassembly must be supervised or completed
by Daikin Applied service personnel. Cost for unit
resassembly and supervision by Daikin Applied service
is not included in the purchase price of the equipment.
Contact Daikin Applied service for pricing.
• Ideal for retrofit applications where it is desired that the
compressor(s), power box, and control box be removed
at the factory, prior to shipment, and where refrigerant
may be secured by others.
POWER BOX
HMI/
OITS PANEL BOX
CONTROL BOX
COMPRESSOR(S)
DETAIL D
COMPRESSOR(S)
DISCHARGE
BLOCKOFF
SUCTION
BLOCKOFF
DETAIL C
DETAIL A
DETAIL B
•
CRATE TO CONTAIN:
DISCHARGE PIPING
•
SUCTION ELBOW
•
MOTOR COOLING
•
LIQUID LINE
•
GLUE
•
LOOSE INSULATION
GLUE
FRONT VIEW
ISOMETRIC
•
MISCELLANEOUS ITEMS
[OPTIONAL]
CRATE TO CONTAIN:
ECONOMIZER
•
PIPING WITH FLANGES
•