IOM 1210-7 • MAGNITUDE
®
MODEL WMC CHILLERS
38 www.DaikinApplied.com
o
peraTIon
Economizer Setpoints
Figure 33: Economizer Setpoint Screen
Table 12: Economizer Setpoint Settings
Description
Default
Range
Password
Comments
Economizer Type
Plate to
Plate
Not Used, Plate to Plate,
Flash Tank
M
Specifies one of two economizer types (plate to plate or flash
tank) if unit is equipped with economizer.
Economizer Open Enable
110
100-120
M
Select setpoint that will enable economizer to open
Economizer Close
105
100-120
M
Select setpoint that will enable economizer to close
Economizer Superheat
Setpoint
6.0 ∆°F
1-10
M
Select setpoint for economizer superheat control