IOM 1210-7 • MAGNITUDE
®
MODEL WMC CHILLERS
58 www.DaikinApplied.com
Controller Inputs and Outputs
The following tables list the controller inputs and outputs, both analog and digital.
Table 25: Controller, Analog Inputs
#
Description
Signal Source
Sensor Range
1
Reset of Leaving Water Temperature
4-20 mA Current
0 to 20°F
2
Entering Evaporator Water Temperature
NTC Thermistor (10k@25°C)
-58 to 212°F
3
Entering Condenser Water Temperature
NTC Thermistor (10k@25°C)
-58 to 212°F
4
Leaving Condenser Water Temperature
NTC Thermistor (10k@25°C)
-58 to 212°F
5
Liquid Line Refrigerant Temperature
NTC Thermistor (10k@25°C)
-58 to 212°F
6
Demand Limit
4-20 mA Current
0-100 %RLA
7
Evaporator Water Flow
4 to 20 mA Current
0 to 10,000 gpm
8
Condenser Water Flow
4 to 20 mA Current
0 to 10,000 gpm
9
Optional Tower Sump Temperature
NTC Thermistor (10k@25°C)
-58 to 212°F
10
Leaving Evaporator Water Temperature
NTC Thermistor (10k@25°C)
-58 to 212°F
NOTE:
“Sensor Range” in
indicates the range of the input, NOT the operating range of the chiller.
Table 26: Controller, Digital Inputs
#
Description
Signal
Signal
1
Unit OFF Switch
0 VAC (Stop)
24 VAC (Auto)
2
Remote Off/Enable
0 VAC (Stop)
24 VAC (Enable)
3
Mode Switch
0 VAC (Normal)
24 VAC (Alternate)
4
Manual Off
0 VAC (Off)
24 VAC (Enable)
5
Manual Off2
0 VAC (Off)
24 VAC (Enable)
6
Manual Off3
0 VAC (Off)
24 VAC (Enable)
7
Manual Off4
0 VAC (Off)
24 VAC (Enable)
8
Quick Off (All Off)
0 VAC (Quick Stop)
24 VAC (Enable)
9
Ground Fault
0 VAC (Alarm)
24 VAC (Off)
10
Ground Fault2
0 VAC (Alarm)
24 VAC (Off)
12
HATS Switch
0 VAC (Off)
24 VAC (Enable)
13
External Fault
Configurable
Configurable
17
Evaporator Water Flow Switch
0 VAC (No Flow)
24 VAC (Flow)
18
Condenser Water Flow Switch
0 VAC (No Flow)
24 VAC (Flow)
Table 27: Controller, Analog Outputs
#
Description
Output Signal
Sensor Range
1
Cooling Tower Bypass Valve Position
0 to 10 VDC
0 to 100% Open
2
Cooling Tower VFD Speed
0 to 10 VDC
0 to 100%
3
EXV signal to IB Valve Control Bd.
0 to 10 VDC
0 to 100%
4
Tower Control Reset
0 to 10 VDC
0 to 100% Mask Reset
5
% Unit Load
0 to 10 VDC
0 to 125% (8V = 100%)
NOTE:
“Sensor Range” in
indicates the range of the output, NOT the operating range of the chiller.