IM 968-4 • MICROTECH III CHILLER UNIT CONTROLLER

Enter Password

1.  If you have not already entered a password and are 

on the Main Menu, turn the circular knob on the unit 

controller (

Figure 10) 

until Enter Password is highlighted 

from the menu list (

Figure 11

). If you have already 

entered a password, skip to Step 3.

2.  Select Enter Password by pressing down on the circular 

knob.

NOTE: 

If you are not at the Main Menu and need to enter 

a password, press the Back button

 

from any other 

menu screen until you reach the Main Menu and then 

follow steps 1-3. 

3.  Enter Password 5321 and then press Enter.

Figure 10: Unit Controller Main Features  

Figure 11: BACnet IP Setup Menu: Enter Password 

4.  Scroll down to View/Set Unit and press Enter

.

5.  Navigate to the LON Setup menu on the unit controller 

keypad display (

Figure 11

)

.

 

Set Receive Heartbeat

1.  Turn the circular knob clockwise to scroll down to 

RecHrtb. Press Enter and then modify as directed by the 

network integrator.

2.  Navigate back to the LON Setup menu. Change any 

other parameters shown in 

Table 3 

as necessary.

NOTE: 

Any changes to network settings are automatically 

saved.

Figure 12: LON Setup Menu

Refer to the MicroTech III Chiller Unit Controller Operation 

Manual (

Reference Documents

) for additional information on 

using the keypad/display to set parameters and defaults for unit 

setpoints. Protocol Document ED 15120 has comprehensive 

descriptions of all 

L

on

W

orks

 variables supported by the 

MicroTech III chiller unit controller (

www.DaikinApplied.com

).

Circular knob  

(press down for Enter)

Back button

Summary of Contents for MicroTech III

Page 1: ...er Unit Controller LonWorks Communication Module Models AGZ and AMZ Trailblazer Air cooled Scroll Chiller Models AWS and AWV Pathfinder Air cooled Screw Chiller Model ADS Air cooled Global Screw Chill...

Page 2: ...sioning and Configuration 10 LonWorks Network Addressing 10 External Interface File XIF and NXE Files 10 Resource Files 10 Commissioning 10 Configuration 10 Enter Password 11 Set Receive Heartbeat 11...

Page 3: ...on 8040_10 LonMark Functional Profile Chiller Version 1 0 www lonmark org Echelon Corporation 078 0156 01G LonWorks FTT 10A Free Topology Transceiver Users Guide www echelon com Limited Warranty Consu...

Page 4: ...geon blue Housing plastic light gray Operating Temperature 40 158 F 40 70 C Humidity 90 RH Atmospheric pressure Min 10 psi 70kPa corresponding to max 9 842 ft 3 000 m above sea level Storage and Trans...

Page 5: ...ule Attached to Unit Controller Figure 4 shows the important features of the LonWorks communication module which are described in the following section Figure 4 LonWorks Communication Module Main Feat...

Page 6: ...icates the communication status between the LonWorks communication module and the network Table 2 Table 2 BUS LED Activity BUS LED Color Description Green The unit controller is capable of communicati...

Page 7: ...pology use one 1 52 3 bus terminator at the busiest point of the network Daisy chain or standard line dual topology use two 2 105 bus terminators at the end of both network segments Repeaters and rout...

Page 8: ...nication module on the unit controller The communication module can be connected directly to the unit controller itself or to an existing module if one is attached 1 Set the Unit On Off Switch to Off...

Page 9: ...ol panel of the unit This must be done prior to replacing a communication module See for switch location 2 Remove power from the unit controller 3 Locate the LonWorks communication module to the left...

Page 10: ...nication module Resource Files Resource files contain definitions of functional profiles network variables types configuration property types and enumerations Resource files are required for displayin...

Page 11: ...net IP Setup Menu Enter Password 4 Scroll down to View Set Unit and press Enter 5 Navigate to the LON Setup menu on the unit controller keypad display Figure 11 Set Receive Heartbeat 1 Turn the circul...

Page 12: ...Minimum Send Time Controls the minimum period of time that expires before certain network variables can be retransmitted nciMinSendTime can also be used to change these values1 Rcv Heartbeat 0 6553 5...

Page 13: ...ved cable Do not use different wire types on the same bus Follow the bus length limits for the cable type Confirm that you have the correct transceiver Make sure that the network trunk avoids strong s...

Page 14: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representativ...

Reviews: