nTroduCTIon

www.DaikinApplied.com 

IM 968-4 • MICROTECH III CHILLER UNIT CONTROLLER

I

nTroduCTIon

This manual contains information regarding the network 

integration system used with MicroTech III unit controllers on 

Daikin Applied chillers. It describes how to install or replace a 

L

on

W

orks

 

communication module on a MicroTech III chiller unit 

controller. It also explains how to set network parameters and 

establish communication between the chiller and 

L

on

W

orks

 

network.

Revision History

IM 968

October 2009

Initial release

IM 968-1

March 2012

Changed OMM 998 to OM 1051. Added 

Model AGZ-D

IM 968-2

January 2017

Updated Daikin branding. Added step 1 to 

set unit switch=off before installing a new 

module. Added AGZ-E and AWV chiller 

models, Troubleshooting section, reference 

to LonMark 3.4 certification, spec table, 

dimensional data, new photos, BSP version, 

and formatting changes

IM 968-3

March 2017

Added AMZ chiller model to data tables, 

Reference Documents, and other 

associated references.

IM 968-4

January 2018

Added WME & WWV chiller models.

Reference Documents

Company

Number Title

Source

Daikin Applied

IOM 1202

Pathfinder

® 

Model AWS Air 

Cooled Chiller Installation, 

Operation, and Maintenance 

Manual

www.

DaikinApplied.

com

Daikin Applied

IOM 1242 

Pathfinder

 

Model AWV Air 

Cooled Chiller Installation, 

Operation, and Maintenance 

Manual

www.

DaikinApplied.

com

Daikin Applied

IOM 1206

Trailblazer

®

 Model AGZ

 

Air 

Cooled Chiller Installation, 

Operation and Maintenance 

Manual

www.

DaikinApplied.

com

Daikin Applied

IOM 1243

Trailblazer

 

Model AMZ Air 

Cooled Chiller Installation, 

Operation, and Maintenance 

Manual

www.

DaikinApplied.

com

Daikin Applied

IOMM 

1033

Magnitude Model WME, B 

vintage Magnetic Bearing 

Centrifugal Chiller Installation, 

Operation, and Maintenance 

Manual

www.

DaikinApplied.

com

Daikin Applied

IOM 1264

Navigator Model WWV 

Water-cooled Chiller 

Installation, Operation, and 

Maintenance Manual

www.

DaikinApplied.

com

Daikin Applied

ED 15120

MicroTech III chiller 

unit controller Protocol 

Information, 

L

on

W

orks

 and 

L

on

W

orks

 Networks

www.

DaikinApplied.

com

LonMark 

Interoperability 

Association

078-0120-

01G

LonMark

®

 Layers 1-6 

Interoperability Guidelines, 

Version 3.4

www.lonmark.

org

LonMark 

Interoperability 

Association

078-0120-

01G

LonMark Application Layer 

Interoperability Guidelines, 

Version 3.4

www.lonmark.

org

LonMark 

Interoperability 

Association

8040_10

LonMark Functional Profile: 

Chiller, Version 1.0

www.lonmark.

org

Echelon 

Corporation

078-0156-

01G

L

on

W

orks

 

FTT-10A Free 

Topology Transceiver Users 

Guide

www.echelon.

com

Limited Warranty

Consult your local Daikin Applied Representative for warranty 

details. To find your local Daikin Applied Representative, go to 

www.DaikinApplied.com

.

Hazardous Information Messages

Recognize Safety Symbols, Words and Labels

The following symbols and labels are used throughout this 

manual to indicate immediate or potential hazards. It is the 

owner and installer’s responsibility to read and comply with 

all safety information and instructions accompanying these 

symbols. Failure to heed safety information increases the 

risk of property damage and/or product damage, serious 

personal injury or death. Improper installation, operation and 

maintenance can void the warranty.

 CAUTION

Cautions indicate potentially hazardous situations, which can result in 

personal injury or equipment damage if not avoided. 
Static sensitive components. Can cause equipment damage.
Discharge any static electrical charge by touching the bare metal inside the 

control panel before performing any service work. Never unplug cables, 

circuit board terminal blocks, or power plugs while power is applied to the 

panel

 WARNING

Warnings indicate potentially hazardous situations, which can result in 

property damage, severe personal injury, or death if not avoided.

 

DANGER

Dangers indicate a hazardous situation which will result in death or 

serious injury if not avoided. Electric shock hazard. Can cause personal 

injury or equipment damage. This equipment must be properly grounded. 

Connections and service to the MicroTech III Unit Controller must be 

performed only by personnel knowledgeable in the operation of the 

equipment being controlled.

 NOTICE

This equipment generates, uses and can radiate radio frequency energy 

and, if not installed and used in accordance with this instruction manual, 

may cause interference to radio communications. It has been tested and 

found to comply with the limits for a Class A digital device, pursuant to 

part 15 of the FCC rules. These limits are designed to provide reasonable 

protection against harmful interference when the equipment is operated in a 

commercial environment. Operation of this equipment in a residential area 

is likely to cause harmful interference in which case the user will be required 

to correct the interference at his or her own expense. Daikin disclaims any 

liability resulting from any interference or for the correction thereof.

Summary of Contents for MicroTech III

Page 1: ...er Unit Controller LonWorks Communication Module Models AGZ and AMZ Trailblazer Air cooled Scroll Chiller Models AWS and AWV Pathfinder Air cooled Screw Chiller Model ADS Air cooled Global Screw Chill...

Page 2: ...sioning and Configuration 10 LonWorks Network Addressing 10 External Interface File XIF and NXE Files 10 Resource Files 10 Commissioning 10 Configuration 10 Enter Password 11 Set Receive Heartbeat 11...

Page 3: ...on 8040_10 LonMark Functional Profile Chiller Version 1 0 www lonmark org Echelon Corporation 078 0156 01G LonWorks FTT 10A Free Topology Transceiver Users Guide www echelon com Limited Warranty Consu...

Page 4: ...geon blue Housing plastic light gray Operating Temperature 40 158 F 40 70 C Humidity 90 RH Atmospheric pressure Min 10 psi 70kPa corresponding to max 9 842 ft 3 000 m above sea level Storage and Trans...

Page 5: ...ule Attached to Unit Controller Figure 4 shows the important features of the LonWorks communication module which are described in the following section Figure 4 LonWorks Communication Module Main Feat...

Page 6: ...icates the communication status between the LonWorks communication module and the network Table 2 Table 2 BUS LED Activity BUS LED Color Description Green The unit controller is capable of communicati...

Page 7: ...pology use one 1 52 3 bus terminator at the busiest point of the network Daisy chain or standard line dual topology use two 2 105 bus terminators at the end of both network segments Repeaters and rout...

Page 8: ...nication module on the unit controller The communication module can be connected directly to the unit controller itself or to an existing module if one is attached 1 Set the Unit On Off Switch to Off...

Page 9: ...ol panel of the unit This must be done prior to replacing a communication module See for switch location 2 Remove power from the unit controller 3 Locate the LonWorks communication module to the left...

Page 10: ...nication module Resource Files Resource files contain definitions of functional profiles network variables types configuration property types and enumerations Resource files are required for displayin...

Page 11: ...net IP Setup Menu Enter Password 4 Scroll down to View Set Unit and press Enter 5 Navigate to the LON Setup menu on the unit controller keypad display Figure 11 Set Receive Heartbeat 1 Turn the circul...

Page 12: ...Minimum Send Time Controls the minimum period of time that expires before certain network variables can be retransmitted nciMinSendTime can also be used to change these values1 Rcv Heartbeat 0 6553 5...

Page 13: ...ved cable Do not use different wire types on the same bus Follow the bus length limits for the cable type Confirm that you have the correct transceiver Make sure that the network trunk avoids strong s...

Page 14: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representativ...

Reviews: