IM 968-4 • MICROTECH III CHILLER UNIT CONTROLLER

Figure 9: Communication Module with Board-to-Board 

Connector Inserted 

6.  Insert the other end of the board-to-board connector to 

the far-left side of the unit controller or other module, if 

attached.

7.  Connect the 

L

on

W

orks

 communication module to 

the network by inserting a network cable into the 

communication module’s network connector (

Figure 4)

.

8.  Apply power to the unit controller.

The unit controller automatically resets itself approximately 

30 seconds after power has been applied to it. This reset is 

necessary so that the 

L

on

W

orks

 communication module can 

synchronize with the unit controller.

NOTE: 

There is a limit of three devices that can be attached 

to the left side of the unit controller.

9.  Set the Unit On/Off Switch to “On” from inside the control 

panel of the unit.

Replacing a Communication Module

Follow these steps to remove an existing 

L

on

W

orks

 

communication module from unit controller and replace it with 

a new module.

1.  Set the Unit On/Off Switch to “Off” from inside the control 

panel of the unit. This must be done prior to replacing a 

communication module. See

 

for switch location.

2.  Remove power from the unit controller.
3.  Locate the 

L

on

W

orks

 communication module to the left 

of the unit controller (

Figure 3

).

4.  Gently pull the network cable connector from the 

L

on

W

orks

 communication module (

Figure 4)

.

5.  Grasp the 

L

on

W

orks

 communication module and 

carefully pull it from the unit controller (or from an 

adjacent module, if it is attached to one.)

6.  Install the new 

L

on

W

orks

 communication module:

a.  Carefully remove the blue plastic knockout strip 

on the right side of the 

L

on

W

orks

 communication 

module.

b.  Insert the board-to-board connector into the 

L

on

W

orks

 communication module. Note that it only 

fits one way and that the baffles must line up with 

corresponding slots in the communication module 

and the unit controller (

Figure 8

 and 

Figure 9

).

7.  Insert the network cable connector into the 

L

on

W

orks

 

communication module (

Figure 4)

.

8.  Apply power to the unit controller.

The unit controller automatically resets itself approximately 

30 seconds after power has been applied to it. This reset is 

necessary so that the 

L

on

W

orks

 communication module can 

synchronize with the unit controller.

9.  Set the Unit On/Off Switch to “On” from inside the control 

panel of the unit.

Summary of Contents for MicroTech III

Page 1: ...er Unit Controller LonWorks Communication Module Models AGZ and AMZ Trailblazer Air cooled Scroll Chiller Models AWS and AWV Pathfinder Air cooled Screw Chiller Model ADS Air cooled Global Screw Chill...

Page 2: ...sioning and Configuration 10 LonWorks Network Addressing 10 External Interface File XIF and NXE Files 10 Resource Files 10 Commissioning 10 Configuration 10 Enter Password 11 Set Receive Heartbeat 11...

Page 3: ...on 8040_10 LonMark Functional Profile Chiller Version 1 0 www lonmark org Echelon Corporation 078 0156 01G LonWorks FTT 10A Free Topology Transceiver Users Guide www echelon com Limited Warranty Consu...

Page 4: ...geon blue Housing plastic light gray Operating Temperature 40 158 F 40 70 C Humidity 90 RH Atmospheric pressure Min 10 psi 70kPa corresponding to max 9 842 ft 3 000 m above sea level Storage and Trans...

Page 5: ...ule Attached to Unit Controller Figure 4 shows the important features of the LonWorks communication module which are described in the following section Figure 4 LonWorks Communication Module Main Feat...

Page 6: ...icates the communication status between the LonWorks communication module and the network Table 2 Table 2 BUS LED Activity BUS LED Color Description Green The unit controller is capable of communicati...

Page 7: ...pology use one 1 52 3 bus terminator at the busiest point of the network Daisy chain or standard line dual topology use two 2 105 bus terminators at the end of both network segments Repeaters and rout...

Page 8: ...nication module on the unit controller The communication module can be connected directly to the unit controller itself or to an existing module if one is attached 1 Set the Unit On Off Switch to Off...

Page 9: ...ol panel of the unit This must be done prior to replacing a communication module See for switch location 2 Remove power from the unit controller 3 Locate the LonWorks communication module to the left...

Page 10: ...nication module Resource Files Resource files contain definitions of functional profiles network variables types configuration property types and enumerations Resource files are required for displayin...

Page 11: ...net IP Setup Menu Enter Password 4 Scroll down to View Set Unit and press Enter 5 Navigate to the LON Setup menu on the unit controller keypad display Figure 11 Set Receive Heartbeat 1 Turn the circul...

Page 12: ...Minimum Send Time Controls the minimum period of time that expires before certain network variables can be retransmitted nciMinSendTime can also be used to change these values1 Rcv Heartbeat 0 6553 5...

Page 13: ...ved cable Do not use different wire types on the same bus Follow the bus length limits for the cable type Confirm that you have the correct transceiver Make sure that the network trunk avoids strong s...

Page 14: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representativ...

Reviews: