background image

OM 1239 

12 www.DaikinApplied.com

Dehumidification

• 

Hot gas reheat with temperature control

 – 

Uses a combination of 2-stage thermostat and 
humidistat to optimize unit capacity and for 
maximum latent capacity while decreasing room 
humidity levels. On a call for cooling, the fan will 
energize, the pump request will energize, the 

45 second flow timer will start. After the flow, 

compressor minimum off, and random startup 
timers are expired, the lead compressor will 
start. If the room setpoint temperature is still not 

satisfied, the lag compressor will be energized 

as the stage 2 cooling settings. When the 

room temperature conditions are satisfied, the 

compressors will shut off and the fan will operate 
according to its "fan only" setting when enabled 
for continuous fan operation. If fan cycling is 
enabled, the fan will turn off, once room setpoint 

conditions are satisfied.

Available operating modes

• 

Occupied

 – The MicroTech III unit controller 

will manage occupied and unoccupied modes 
of operation. The occupancy mode can 
be established by a BACnet or 

L

on

W

orks

 

communication signal, from a room sensor 
equipped with “Occupied/Unoccupied” mode 
functions, or a thermostat equipped with an 
“Occupied/Unoccupied” mode switch. When in 
the occupied mode, the unit will be controlled to 
its occupied setpoint conditions. The occupancy 
state will be displayed on sensors equipped with 
“Occupied/Unoccupied” mode functions and 
annunciation capabilities.

• 

Unoccupied 

– When operating in the unoccupied 

mode, the unit will be controlled to its unoccupied 
setpoint conditions and the fan will cycle 

according to a call for cooling, dehumidification 

or heating. A simple “grounded” signal between 
terminals U and C on the MicroTech III unit 
controller will place the unit into the unoccupied 
mode for night setback operation. The occupancy 
state will be displayed on sensors equipped with 
“Occupied/Unoccupied” mode functions and 
annunciation capabilities.

• 

Override

 – A momentary (4 to 9 seconds) press 

of the “Override” button on the thermostat or 
room sensor during the unoccupied mode will 
cause the unit to operate in the occupied mode 
for two hours, for after-hours heating, cooling or 

dehumidification. “OVERRIDE” will be displayed 

on sensors equipped with override button and 
annunciation capabilities.

• 

Standby mode

 – BACnet or 

L

on

W

orks

 units 

can receive a signal from the Building Automation 
System (BAS) to initiate the energy savings mode. 
This mode is typically initiated by the BAS with 
smart grid technologies to save energy. The savings 
is driven by reducing peak electrical demand for 
the building. Once initiated, the MicroTech III unit 
controller will reset its effective setpoint to minimize 
the stage of compressor operation. “E-SAVE” will be 
displayed on sensors equipped with bypass mode 
annunciation capabilities.

• 

Emergency unit shutdown

 – A simple grounded 

signal puts the unit into the shutdown mode. 
Remote shutdown is provided so that when 
properly connected to a water loop controller or 
remote switch, the emergency shutdown input 
can be used to shut down the water source 
heat pump. Compressor and fan operations are 
suspended, and an a unique two external LED 
status is generated.

MicroTech III unit protection

The control inputs are High Pressure (HP1/HP2), Low 
Pressure (LP1/LP2), Suction Line Temperature Sensor 

(SLTS1/SLTS2), Condensate Overflow (COF), freeze 

fault, Unoccupied (U), and Remote Shutdown (E). The 
control inputs are in normal states during occupied mode. 
The state of each control in occupied mode during normal 
operation is as follows:

• 

High pressure (HP1/HP2):

 Normally closed 

switch that opens on a high refrigerant pressure 
condition. Control will generate a high pressure fault 
and disables the compressor output on the circuit 
where the switch is open. Upon a failure of the 
lead compressor, it will be "fail replaced" by the lag 
compressor if available.

• 

Low pressure (LP1/LP2):

 Normally closed switch 

that opens on a low refrigerant pressure condition. 
Control will generate a low pressure fault on the 
circuit where the switch is open.

• 

Short cycle protection & random start –

 After 

power cycle or deactivation of certain alarms, 
or when leaving the unoccupied mode, a new 
random compressor start-delay time between 300 
and 360 seconds is generated. The random start 
timer prevents compressors in different units from 
starting simultaneously. Compressor minimum 
OFF 360 sec) and compressor minimum ON (180 
sec) timers prevent compressor short cycling.

• 

Suction line temperature sensor (SLTS1/SLTS2)

The control module will monitor the SLT sensor and 
if the refrigerant temperature drops below the low 
temperature limit set point, the controller will go into 
the low temperature fault mode.

M

ICro

t

eCh

 III u

nIt

 C

ontroller

Summary of Contents for MicroTech III

Page 1: ...MicroTech III Unit Controller with I O Expansion Module for Two Compressor Water Source Heat Pumps Large Capacity Vertical Models LVC Standard Range LVW Extended Range Large Capacity Horizontal Models...

Page 2: ...nd LED annunciation 14 A and IV PR H8 16 Fault recovery and reset 17 Fan operation during most modes faults and shutdowns 19 Faults and modes 19 Microtech III unit controller interface to external equ...

Page 3: ...nication module Each option features direct quick connect wiring to all unit controlled components for clean wiring inside the control box Each control circuit board receives power from a 75VA transfo...

Page 4: ...ubleshooting and diagnosis of the second circuit Allows for Control of second refrigeration circuit LonWorks Communication Module The MicroTech III control system accepts a plug in LonWorks commu nica...

Page 5: ...rsing Valve Common H6 7 Reversing Valve Output H7 1 1 No Connection H7 2 No Connection H7 3 Red LED Output H7 4 Green LED Output H7 5 Yellow LED Output H7 6 Red Green Yellow LED Common H8 1 1 Isolatio...

Page 6: ...OM 1239 6 www DaikinApplied com MicroTech III Unit Controller Figure 1 MicroTech III unit controller terminal locations...

Page 7: ...Economizer Output N O H3 4 Ext 24 VAC Common H3 5 Fan Motor Signal H3 6 Fan Motor Common H4 1 1 Entering Water Temp Sensor Signal H4 2 Entering Water Temp Sensor Common H5 1 1 No Connection H5 2 No Co...

Page 8: ...PI_SELECT1_0 SPI Select To Communications Board CN_SPI 4 SPI_CLK_0 Master Clock CN_SPI 5 SPI_RX_0 MOSI CN_SPI 6 SPI_TX_0 MISO CN_SPI 7 SREADY_0 SPI Ready To Baseboard CN_SPI 8 No Connection TB1 1 TB1...

Page 9: ...re cycling power to the controller or sending a controller a reboot command through the network communications Table 6 MicroTech III controller configuration jumper settings Baseboard Description Jump...

Page 10: ...Open Secondary Heating Options JP3 JP4 JP3 Open None JP4 Open JP3 Shorted Supplemental Electric Heat JP4 Open JP3 Open Boilerless Electric Heat JP4 Shorted Cooling Dehumidification Options JP5 JP6 JP...

Page 11: ...hru activation of the G terminal by the thermostat fan switch on On a further demand for cooling stage 2 the 1st compressor will start in the cooling mode On a further demand for cooling the second co...

Page 12: ...annunciation capabilities Standby mode BACnet or LonWorks units can receive a signal from the Building Automation System BAS to initiate the energy savings mode This mode is typically initiated by the...

Page 13: ...no anti freeze in the cooling heating modes and extended range applications in the cooling mode or 13 5 F LWT on extended range applications in the heating mode those with anti freeze Defrost process...

Page 14: ...r will energize in place of the failed lead compressor when the lag compressor minimum OFF timer has expired Reversing valve for the lag compressor will be positioned if necessary 5 seconds after the...

Page 15: ...condensate overflow mode See Table 10 on page 19 When the unit senses a condensate overflow fault while in cooling mode the following occurs The compressors de energize The fault terminal A energizes...

Page 16: ...rmal operation When the E terminal is no longer grounded the unit will automatically return to normal operation Note The remote shutdown input E will suspend unit operation Disconnect power when servi...

Page 17: ...clears faults the first two times they occur within a 24 hour period and triggers an automatic lockout on the 3rd fault The fault remains active until the alarm is manually cleared At the end of the...

Page 18: ...terminal wiring Refer to MicroTech III unit controller and I O expansion module connector terminal tables and descriptions on page 5 MicroTech III unit controller terminal locations on page 6 3 The le...

Page 19: ...is left on after system check out the unit may be damaged Table 9 Room sensor status LED LED On Time Sec LED Off Time Sec Operating Mode 0 5 0 5 Alarm Condition or Network Wink Operation Active 0 0 Co...

Page 20: ...FF ON Compressor 1 Suction Temp Sensor Fail Fault Flash Flash ON Freeze Fault Detect Fault Flash OFF Flash Compressor 1 Low Suction Temp Fault Flash OFF OFF Room Temp Sensor Fail Room Sensor Control O...

Page 21: ...ostat or control inputs To interface triacs or other solid state switching devices to the MicroTech III unit controller inputs separate them from the board using mechanical relays To do this use the t...

Page 22: ...OFF OFF Flash Compressor 2 Low Pressure LP2 Fault OFF OFF ON Compressor 2 Low Suction Temp LT2 Sensor Fail Fault Flash Flash ON Compressor 2 Low Suction Temp LT2 Fault Flash OFF OFF Entering Water Te...

Page 23: ...is needed the humidistat can be wired to TB1 1 on the Microtech III unit controller allowing the WSHP unit to operate in dehumidification mode only The unit will only respond to a call for dehumidific...

Page 24: ...DC Signal Common Fan Speed Se lect Fan Coil Version Only Emergency Shutdown Unoccupied Dehumidifica tion Sensor Digitally Adjustable Room Temperature Sensor Part No 910121754 Figure 13 MicroTech III b...

Page 25: ...d return air discharge air and leaving water temperature sensor Wall mounted temperature sensors include setpoint adjustment and tenant override The user has the capability of substituting the wall se...

Page 26: ...Four green status LEDs on the communication module indicate communication activity on the MS TP communication network and with the unit controller Figure 15 MicroTech III BACnet MS TP snap in communic...

Page 27: ...4V NO 24VAC COMMON 24V NC Note Switch L2 L3 fan motor wires for left hand unit Legend Item Description CC1 Circuit 1 Compressor Contactor CC2 Circuit 2 Compressor Contactor CM1 Circuit 1 Compressor CM...

Page 28: ...OOL 2 W1 HEAT 1 W2 HEAT 2 A ALARM OUTPUT 5 DC SIGNAL COM 4 ROOM SENSOR TO 3 SETPOINT ADJUST 2 FAN MODE HT CL AUTO 1 ROOM SENSOR LED U MARK IV OCC UNOCC E EMER SHTDN INPUT R 24VAC Communication Module...

Page 29: ...Switch L2 L3 fan motor wires for left hand unit Note Wiring diagrams are typical For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the un...

Page 30: ...HTDN INPUT R 24VAC Communication Module MicroTech III Controller 24V NO 24VAC COMMON 24V NC Note Switch L2 L3 fan motor wires for left hand unit Note Wiring diagrams are typical For the latest drawing...

Page 31: ...oose connection Check for faulty compressor capacitor Insufficient cooling or heating Check for lock rotor amp draw Check for defective compressor internal windings with ohm meter Check for proper air...

Page 32: ...t to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative...

Reviews: