OM 1239
20 www.DaikinApplied.com
M
ICro
t
eCh
III u
nIt
C
ontroller
Table 11: MicroTech III unit controller status LED's
Description
Type
Yellow
Green
Red
IO Expansion Communication Fail
Fault
ON
Flash
Flash
Invalid Jumper Configuration
Fault
Flash
Flash
OFF
Low Voltage Brownout
Fault
OFF
Flash
OFF
Emergency Shutdown
Mode
OFF
Flash
OFF
Compressor #1 High Pressure
Fault
OFF
OFF
Flash
Compressor #1 Low Pressure
Fault
OFF
OFF
ON
Compressor #1 Suction Temp Sensor Fail
Fault
Flash
Flash
ON
Freeze Fault Detect
Fault
Flash
OFF
Flash
Compressor #1 Low Suction Temp
Fault
Flash
OFF
OFF
Room Temp Sensor Fail (Room Sensor Control Only)
Fault
Flash
Flash
ON
Leaving Water Temp Sensor Fail (Freeze Fault Protect)
Fault
Flash
Flash
ON
Condensate Overflow (Cooling & Dehumidification Modes)
Fault
ON
OFF
OFF
Serial EEPROM Corrupted
Fault
ON
ON
ON
Waterside Economizer Low Temp Cutout
(WSE Control & Call for Cooling)
Mode
Flash
ON
Flash
Service Test Mode Enabled
Mode
Flash
Flash
Flash
Unoccupied Mode
Mode
ON
ON
OFF
Occupied, Bypass, Standby, Modes
Mode
OFF
ON
OFF