D
–EOMWC00A07-16_02EN
Operation Manual
30/77
Model
Name plate
F3AS
HSA192
F3AL
HSA204
F3BS
HSA215
F3BL
HSA232
F4AS
HSA241
F4AL
HSA263
The required capacity is achieved by controlling one modulating slide and one non-modulating slide. The modulating slide
can control 10% to 50% of the total compressor capacity, infinitely variable. The non-modulating slide can control either
0% or 50% of the total compressor capacity.
Either the load or the unload solenoid for the non-modulating slide is on any time the compressor is running. For
compressor capacity from 10% up to 50%, the non-modulating slide unload solenoid is on to keep that slide in the unloaded
position. For capacity from 60% to 100%, the non-modulating slide load solenoid is on to keep that slide in the loaded
position.
The modulating slide is moved by pulsing of the load and unload solenoids to achieve the required capacity.
An additional solenoid is controlled to assist in moving the modulating slide in certain conditions. This solenoid is activated
when the pressure ratio (condenser pressure divided by evaporator pressure) is less than or equal to 1.2 for at least 5
seconds. It is deactivated when pressure ratio is more than 1.2.
Slide Control Solenoids (Symmetric compressors)
This section applies to the following compressor models (asymmetric):
Model
Name plate
F4221
HSA205
F4222
HSA220
F4223
HSA235
F4224
HSA243
F3216
HSA167
F3218
HSA179
F3220
HSA197
F3221
HSA203
F3118
HSA3118
F3120
HSA3120
F3121
HSA3121
F3122
HSA3122
F3123
HSA3123
The required capacity is achieved by controlling one modulating slide. The modulating slide can control 25% to 100% of
the total compressor capacity, infinitely variable.
The modulating slide is moved by pulsing of the load and unload solenoids to achieve the required capacity.