D
–EOMWC00A07-16_02EN
Operation Manual
38/77
10.4.3
Evaporator Flow Loss
This alarm is generated in case of flow loss to the chiller to protect the machine against Mechanical High Pressure trips.
Symptom
Cause
Solution
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display. String in the alarm list:
UnitOffCondWaterFlow String in the
alarm log:
UnitOffCondWaterFlow
String in the alarm snapshot
UnitOffCondWaterFlow
No water flow sensed for 3 minutes
continuously or water flow too low.
Check the water pump filler and the
water circuit for obstructions.
Check the flow switch calibration and
adapt to minimum water flow.
Check if pump impeller can rotate
freely and has no damages.
Check pumps protection devices
(circuit breakers, fuses, inverters,
etc.)
Check if water filter is clogged.
Check flow switch connections.
Reset
Notes
Local HMI
Network
Auto
10.4.4
Evaporator Water Freeze Protect
This alarm is generated to indicate that the water temperature (entering or leaving) has dropped below a safety limit.
Control tries to protect the heat exchanger starting the pump and letting the water circulate.
Symptom
Cause
Solution
Unit status is Off.
Water flow too low.
Increase the water flow.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display. String in the alarm list:
UnitOffEvapWaterTmpLo
String in the alarm log:
UnitOffEvapWaterTmpLo
String in the alarm snapshot
UnitOffEvapWaterTmpLo
Inlet temperature to the evaporator is
too low.
Increase the inlet water temperature.
Flow switch is not working or no water
flow.
Check the flow switch and the water
pump.
Sensors readings (entering or leaving)
are not properly calibrated.
Check the water temperatures with a
proper instrument and adjust the
offsets.
Wrong freeze limit setpoint.
The freeze limit has not been changed
as a function of glycol percentage.
Reset
Notes
Local HMI
Network
Auto
It’s required to check if the evaporator
has any damage due to this alarm.