63/77
Operation Manual
D
–EOMWC00A07-16_02EN
11 BASIC CONTROL SYSTEM DIAGNOSTIC
MicroTech controller, extension modules and communication modules are equipped with two status LED (BSP and BUS)
to indicate the operational status of the devices. The meaning of the two status LED is indicated below.
Controller LED
BSP LED
BUS LED
Mode
Solid Green
OFF
Application running
Solid Yellow
OFF
Application loaded but not running (*)
Solid Red
OFF
Hardware Error (*)
Flashing Yellow
OFF
Application not loaded (*)
Flashing Red
OFF
BSP Error (*)
Flashing Red/Green
OFF
Application/BSP update
(*) Contact Service.
Extension Module LED
BSP LED
BUS LED
Mode
Solid Green
BSP running
Solid Red
Hardware Error (*)
Flashing Red
BSP Error (*)
Solid Green
Communication running, I/O working
Solid Yellow
Communication running, parameter missing (*)
Solid Red
Communication down (*)
(*) Contact Service.
Extension Module EXV Driver
Open LED
Close LED
Status
Off
Off
Valve not moving
On
Off
Valve full open (not applicable)
Off
On
Valve full closed
Off
Flashing
Valve closing or going to reference after power fail
Flashing
Off
Valve opening
Flashing
Flashing
Motor disconnected or shorted
Communication Module LED
BSP LED
Mode
Solid Green
BPS running, communication with controller
Solid Yellow
BSP running, no communication with controller (*)
Solid Red
Hardware Error (*)
Flashing Red
BSP Error (*)
Flashing Red/Green
Application/BSP update
(*) Contact Service.
BUS LED status vary depending on the module.
LON module:
BuS LED
Mode