71/77
Operation Manual
D
–EOMWC00A07-16_02EN
Figure 17, Navigation, Part B
View/Set Unit
Status/Settings
Power Conservation (view/set unit)
Set-Up
Unit Capacity
R
Temperatures
Unit Current
R
Condenser
Demand Limit Enable
R/W
Date/Time/Schedules
Demand Limit Value
R
Power Conservation
Current @ 20mA
R
LON Setup
Current Limit Setpoint
R
BACnet IP Setup
Setpoint Reset
R/W
BACnet MSTP Setup
Max Reset
R/W
Modbus Setup
Start Reset DT
R/W
AWM Setup
Soft Load Enable
R/W
Soft Load Ramp
R/W
Design Conditions
Starting Capacity
R/W
Alarm Limits
Menu Password
LON Setup (view/set unit)
Neuron ID
R
View/Set Circuit
Max Send Time
R/W
Min Send Time
R/W
Status/Settings
Receive Heartbeat
R/W
Compressor
LON BSP
R
LON App Version
R
Time Until Restart
BACnet IP Setup (view/set unit)
Compressor 1 Cycle Time
Remaining
R
Apply Changes
R/W
Compressor 2 Cycle Time
Remaining
R
Name
R/W
Compressor 3 Cycle Time
Remaining
R
Dev Instance
R/W
Compressor 4 Cycle Time
Remaining
R
UDP Port
R/W
DHCP
R/W
Alarms
Actual IP Address
R
Alarm Active
Actual Mask
R
Alarm Log
Actual Gateway
R
Given IP Address
R/W
Scheduled Maintenance
Given Mask
R/W
Next Maintenance Month/Year
R/W
Given Gateway
R/W
Service Support Reference
R
Unit Support
R/W
NC Dev 1
R/W
NC Dev 2
R/W
About This Chiller
NC Dev 3
R/W
Model Number
R
BACnet BSP
R
G. O. Number
R
Unit Serial Number
R
BACnet MSTP Setup (view/set
unit)
BACnet
MSTP
Setup
(view/set
unit)
Starter Model Number(s)
R
Apply Changes
R/W
Starter Serial Number(s)
R
Name
R/W
Firmware Version
R
Dev Instance
R/W
Application Version
R
MSTP Address
R/W
Application GUID
R
Baud Rate
R/W
HMI GUID
R
Max Master
R/W
OBH GUID
R
Max Info Frm
R/W
Unit Support
R/W
Term Resistor
R/W
NC Dev 1
R/W
NC Dev 2
R/W
NC Dev 3
R/W
BACnet BSP
R
Modbus Setup (view/set unit)
Apply Changes
R/W
Address
R/W
Parity
R/W
Two Stop Bits
R/W
Baud Rate
R/W
Load Resistor
R/W
Response Delay
R/W
Comm LED Time Out
R/W