C
omprehensIve
d
aTa
T
ables
www.DaikinApplied.com 19
ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER
Table 11:
Binary Values - SmartSource Single and Two Stage, Enfinity Large Two Compressor
Point Name
Object
Type/
Instance
Read/
Write
Access
2
BACnet Object
Name
Range/Default
(in Units)
Non-
volatile
Memory
1
Description
BINARY VALUES
Clear Alarm
BV:1
W
ClearAlarm
0 to 1
Default: 0
N
Clears the Current Alarm. The alarm that is cleared moves
to the Previous Alarm buffer. Value automatically clears
after a clear alarm command is issued.
0 = Normal
1 = Clear Alarm
Binary Output Status
BV:2
R
BinaryOut
(Description
Property)
16 bits
N
Monitors the digital outputs of the unit controller for
diagnostic purposes. Each item is reported as a bit so
that multiple outputs can be viewed simultaneously. The
Present_Value reflects the first status bit (b0), which is the
“Compressor #1” state. All the status bits are returned in
the BV2.description property, high bit on the left and low
bit on the right. Example: 0000000000000001 indicates
that the compressor #1 output is active. Array index NULL
Selected Parameters Information
for bit descriptions.
Table 12:
Multi-State Inputs - SmartSource Single and Two Stage, Enfinity Large Two Compressor
Point Name
Object
Type/
Instance
Read/
Write
Access
2
BACnet Object
Name
Range/Default
(in Units)
Non-
volatile
Memory
1
Description
MULTI-STATE INPUTS
Condensate Overflow
Status
MSI:1
R
CondOverFlow
1 to 3
N
Monitors the condensate overflow sensor input.
1 = Dry
2 = Wet
3 = Null (no sensor present)
Fan ON/Auto Switch
Status
(Room Sensor)
MSI:2
R
FanOnAuto
1 to 3
N
Displays the room sensor fan On/Auto switch position.
1 = On
2 = Auto
3 = Null (no switch present)
System Mode Switch
(Heat/Cool/Auto)
Status
MSI:3
R
HeatCoolAuto
1 to 5
N
Displays the room sensor System Mode switch
(Heat/Cool/Auto) position.
1 = Off
2 = Heat
3 = Cool
4 = Auto
5 = Null (no switch present)
Humidistat Sensor
Status
MSI:4
R
Humidistat
1 to 3
N
Status of the Humidistat/Cooling Stage #1 sensor input.
Signal input represents “Humidistat” for units with the HGR
option. Otherwise, this value represents the thermostat
“Cooling Stage #1” request.
1 = Not Humid (Inactive 24VAC Input)
2 = Is Humid (Active 24VAC Input)
3 = Null
Fan Running Output
MSI:5
R
FanRunStatus
1 to 2
N
Commanded fan run status. MSI-5 is used in conjunction
with AV38 to indicate the Fan Runtime and Fan Speed
status.
Fan OFF/ON Command:
1 = Fan is off
2 = Fan is running