MTB 158 Microprocessor Thermostat

ON/OFF and 3-Wire Controller

 

DANGER

READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE 

THIS THERMOSTAT. 
Failure to observe safety information and comply with 

instructions could result in PERSONAL INJURY, DEATH 

AND/ OR PROPERTY DAMAGE. 
To avoid electrical shock or damage to equipment, 

disconnect power before installing or servicing. Use only 

wiring with insulation rated for full thermostat operating 

voltage. Use copper wire only. Insulate or wirenut all un-

used leads. Any wiring, including the remote probe,may 

carry the full operating voltage of the thermostat. 

To  avoid  potential  fire  and/  or  explosion  do  not  use  in 

potentially flammable or explosive atmospheres. 

Retain these instructions for future reference. You must 

review your application and national and local codes to 

ensure that your installation will be functional and safe. 

 CAUTION

Care should be used to avoid electrostatic discharge to 

the microprocessor. 

This  unit  has  configuration  jumpers.  You  may  need  to 

reconfigure this thermostat for your application.

Installation 

1.  Install the thermostat with the two furnished mounting 

screws to a standard 4-11/16" × 2-1/8" square device 

box with a 2" × 4" adapter ring. 

2.  For wall installations, mount the thermostat on an 

inside wall approximately 5 feet above the floor. The 

location should provide circulation at average room 

temperature. Avoid direct sunlight or sources of hot or 

cold air in the room or wall. 

3.  Remove the cover. Mount thermostat base assembly 

to the outlet box using the screws provided, tighten 

the screws evenly but do not over tighten. Connect 

wires as shown in the appropriate wiring diagram for 

your thermostat style. 

4.  To use a remote sensor on units with local sensing 

capability, remove jumper JP-1 to disable local 

sensing. Failure to remove JP-1 will cause improper 

operation of the thermostat. 

5.  Remove the LCD plastic protective film. Reinstall 

the cover assembly. Install the cover locking screw 

provided in the hole at the left side of the control 

enclosure to complete the installation. 

6.  Checkout: After wiring and installation are complete, 

energize the system and check the operation. Adjust 

the thermostat as necessary to complete at least one 

cycle. Be sure the thermostat and all other equipment 

are functioning correctly. 