High Condenser Pressure Delay
5 sec
0 to 5 sec
Low Pressure Ratio Delay
300 sec
30 to 300 sec
Start Time Limit
60 sec
20 to 180 sec
Low DSH Limit
10.8°F (6.0°C)
3.6 to 27.0°F (2.0°C to 15.0°C)
BAS Control Inputs
Network Unit Enable
Disable
Disable, Enable
Network Cool Set Point
44.6°F (7.0°C)
See below section
Network Capacity Limit
100%
0% to 100%
Network Alarm Clear Command
Normal
Normal, ClearAlarm
Table 19: Unit Test Mode Set Points
Description
Default
Range
Test Unit Alarm Output
Off
Off, On
Test Evaporator Pump Output 1
Off
Off, On
Test Evaporator Pump Output 2
Off
Off, On
Test Condenser Pump Output 1
Off
Off, On
Test Condenser Pump Output 2
Off
Off, On
Test Cooling Tower Fan 1 Output
Off
Off, On
Test Cooling Tower Fan 2 Output
Off
Off, On
Test Cooling Tower VFD Speed
0.0%
0.0% to 100.0%
Test Cooling Tower Bypass Valve Position
0.0%
0.0% to 100.0%
NOTE:
Unit test mode set points can be changed only when the unit mode is Test. When the unit mode is no longer Test, all unit
test mode set points will be changed back to the ‘off’ values.
Table 20: Administration and Service Support
Description
Default
Range
Unit G.O. Number
“Enter Data”
Alphanumeric string of up to 16 characters
Unit Serial Number
“Enter Data”
Alphanumeric string of up to 20 characters
Next Maintenance Month
January
January through December
Next Maintenance Year
2017
2009 - 2200
Service Support Reference
999-999-9999
Any 10 digit phone number
Controller Time
From Controller Timeclock
00:00:00 to 23:59:59
Controller Date
From Controller Timeclock
1/1/2000 to 12/31/2050
UTC Difference
-60 minutes
-3276 to 32767 minutes
Daylight Savings Time Enable
Yes
No, Yes
Daylight Savings Time Start Month
March
January through December
Daylight Savings Time Start Week
2nd Week
1st through 5th Week
Daylight Savings Time End Month
November
January through December
Daylight Savings Time End Week
1st Week
1st through 5th Week
Operator Password Disable
Off
Off, On
Apply Changes
No
No, Yes
Active Alarm Clear
Off
Off, On
Alarm Log Clear
No
No, Yes
Alarm Log Export
No
No, Yes
Power Restore Event Log - Day Selection
Current
Current, 2nd Day, 3rd Day, 4th Day, 5th Day, 6th Day, 7th Day
Display Units
English
English, Metric