Pressure Drop Data
Table 13: Evaporator Flow Limits
NOTE:
Flow rates and pressure drops reflect water only and do not
apply to glycol solutions.
Figure 62: Model ACH1000DQ
Figure 63: Model EV4027
EVAP
Minimum
Maximum
gpm
ft H
gpm
ft H
ACH1000DQ-166AH
157.0
1.7
528.0
17.1
ACH1000DQ-206AH
197.0
2.0
660.0
16.9
ACH1000DQ-250AH
239.0
2.0
766.0
16.8
ACH1000DQ-330AH
315.0
2.3
925.0
16.9
EV4027A10/09
148.8
2.1
595.7
26.7
EV4027F10/10
120.5
2.2
585.0
34.5
EV4027A11/07
188.0
2.0
748.0
26.0
EV4027F11/08
152.3
2.2
585.0
21.7
EV4027A12/07
188.0
2.3
748.0
28.1
EV4027F12/08
152.3
2.5
585.0
22.8
EV5027A14/07
219.3
2.4
876.6
28.4
EV5027F14/08
189.8
2.8
774.6
29.6
EV5027A17/05
290.6
2.6
1171.2 30.4
EV5027F17/06
245.5
3.2
1060.0 38.3
EV5039A12/11
207.8
3.0
834.8
35.7
EV5039F12/12
186.5
3.6
766.1
39.7
EV6633A15/07
336.4
2.7
1329.7 30.4
EV6633F15/08
249.9
2.5
1450.0 43.1
EV6633F16/06
301.2
1.5
1395.0 22.2
EV6639A14/11
260.6
3.7
1042.6 40.6
EV6639F14/12
204.6
3.1
958.2
40.6
EV6639A16/09
317.4
3.7
1261.9 41.6
EV6639F16/10
277.6
3.9
1140.2 41.2
EV6639A17/07
398.5
2.7
1586.8 32.3
EV6639F17/08
341.7
3.5
1403.9 37.5
0
10
20
100
200
300
400
500
600
700
800
900
1000
Pre
ss
ure
Dro
p (
ft)
Flow Rate (gpm)
Evaporator ACH1000DQ
ACH1000DQ-166AH
ACH1000DQ-206AH
ACH1000DQ-250AH
ACH1000DQ-330AH
0
10
20
30
40
100
200
300
400
500
600
700
800
Pre
ss
ure
Dro
p (
ft)
Flow Rate (gpm)
Evaporator EV4027
EV4027A10/09
EV4027F10/10
EV4027A11/07
EV4027F11/08
EV4027A12/07
EV4027F12/08
Pressure Drop Data