Installation and Application Considerations
www.DaikinApplied.com 25
IOM 1242-8 • PATHFINDER
®
MODEL AWV CHILLERS
Figure 47: Field Wiring Diagram - Multiple Point Power
4-20 mA
DEMAND LIMIT
(BY OTHERS)
4-20 mA
SETPOINT OVERRIDE
(BY OTHERS)
_
_
+
+
EA1
** USE DRY CONTACTS ONLY, SEE NOTE 2
IF EXTERNAL ALARM IS USED, REMOVE
LEAD 402 BETWEEN M5 TERMINALS 5 & 15
TIME
CLOCK
OFF
MANUAL
ON
AUTO
OPTIONAL
FIELD SUPPLIED
CONTROL POWER
OPEN Q12 IF SUPPLY IS SEPARATE 120 VAC SOURCE
DISCONNECT
(BY OTHERS)
N
120 VAC
115
VAC
F120
T1
F120
37
M5
REMOTE
SWITCH
(BY OTHERS)
M5
M5
M5
M5
M5
M5
M5
** USE DRY CONTACTS ONLY, SEE NOTE 2
IF REMOTE SWITCH IS USED,
REMOVE MECHANICAL JUMPER
BETWEEN M5 TERMIONALS 58 & 59.
38
35
5
58
36
15
59
EXTERNAL
ALARM
N
N
120 VAC
120 VAC
EVAP. WATER
PUMP RELAY No. 2
(BY OTHERS)
M5
MQ
M5
MQ
CHWR2
(BY OTHERS)
EVAP. WATER PUMP RELAY
120VAC @ 0.25AMP MAX
49
CHWR1
(BY OTHERS)
EVAP. WATER PUMP RELAY
120VAC @ 0.25AMP MAX
28
17
17
EVAP. WATER
PUMP RELAY No. 1
(BY OTHERS)
3 PHASE
POWER
SOURCE
POWER BLOCK
OR
DISCONNECT SWITCH
MODE SWITCH
** USE DRY CONTACTS ONLY, SEE NOTE 2
IF MODE SWITCH IS USED, REMOVE
LEAD 322 BETWEEN M5-21 AND MS-10.
57
21
M5
M5
TO
COMPRESSOR(S)
AND FAN MOTORS
OR CIRCUIT 1
CIRCUIT BREAKER
(BY OTHERS)
12
MQ
MQ
17
EARTH
GROUND
(BY OTHERS)
FUSE
20A for 2KVA
30A for 3KVA
Q12
NOTE:
1) ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1 WIRING
SYSTEM WITH CONDUCTOR RATED
600 VOLTS.
2)**=USE "DRY CONTACTS" ONLY.
DO NOT SUPPLY FIELD POWER TO
THIS CIRCUIT.
3)DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.
4)COMMUNICATION CARD WIRING IS
SHOWN ON THE AWV KIT DRAWING
INDEX PAGE 13/14.
3 PHASE
POWER
SOURCE
TO
COMPRESSOR
AND FAN MOTORS
CIRCUIT 2
CIRCUIT BREAKER
(BY OTHERS)
POWER BLOCK OR
DISCONNECT SWITCH
23
M5
M5
8
NOTE: For Factory Supplied Thermal
Dispersion Flow Switch wiring, see wiring
instruction in Kit.
FLow Switch Contacts
M
DI2
**USE DRY CONTACS ONLY
SEE NOTE 2
N
120 VAC
M5
MQ
ABR
(BY OTHERS)
120VAC @ 0.25AMP MAX
Bell
Alarm
Option
26
17
N
120 VAC
M5
MQ
44
17
WSESR
(BY OTHERS)
N
120 VAC
M5
MQ
45
11
WATER SIDE
ECONOMIZER
STATUS RELAY
IF WATER SIDE ECONOMIZER
IS
USED,
REMOVE LEAD 552 AND
INSTALL SWITCH BETWEEN
M5-45 AND MQ-11
* SEE NOTE 2
*120VAC CIRCUIT
WATER SIDE
ECONOMIZER
ENABLE
T1
L3
T3
L1
PANEL
T2
L2
T1
L3
T3
L1
T2
L2
(933)
(928)
(837)
(930)
(818)
(820)
(835)
(835)
(821)
(933)
(947)
Note: Separate grounding is
required if fed from different
transformers. Otherwise a
single ground is acceptable.