Install the lower air outlet assembly in the correct location. Install and tighten
the 2 screws.
a
a
b
c
f
f
g
d
e
a
Screw (upper air outlet assy)
b
Upper air outlet assy
c
Drain hose
d
Damper motor wiring harness
e
Screw (tie strap)
f
Screw (lower air outlet assy)
g
Lower air outlet assy
13
Route the damper motor wiring harness through the appropriate harness
retainers.
14
Install the screw to connect the tie strap to the unit.
15
Connect the drain hose to the lower air outlet assembly.
16
Install the drain hose fixation bracket. Install and tighten the screw.
17
Install the upper air outlet assembly in the correct location. Install and tighten
the 2 screws.
18
153].
19
Perform a pressure test on the piping of the indoor unit and vacuüm. Open
the stop valves when done.
20
Add
refrigerant
to
the
refrigerant
circuit,
see
Is the problem solved?
Action
Yes
No further actions required.
No
of the indoor unit fan motor and
continue with the next procedure.
4.9 Indoor unit main PCB
4.9.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.