4
|
Components
Service manual
108
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
Is the measured voltage on the indoor
unit main PCB correct?
Action
No
Continue with the next step.
3
Measure the output voltage between the pins 1‑4 of the connector S102 on
the indoor unit power PCB.
Result:
The measured voltage MUST be 324 V DC.
Output voltage on indoor unit power
PCB correct?
Action
Yes
Correct the wiring between the indoor
unit main PCB and indoor unit power
PCB, see
No
Perform a check of the indoor unit
power PCB, see
To check the HAP LED of the indoor unit main PCB
INFORMATION
HAP LED is ONLY available on the main PCB of the floor standing indoor units.
Prerequisite:
First perform a power check of the indoor unit main PCB, see
106].
1
Locate the HAP LED on the indoor unit main PCB.
a
a
HAP LED
INFORMATION
Make sure the correct software is available on the PCB. If NOT, update using the
updater tool.