4
|
Components
Service manual
128
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
Is the problem solved?
Action
No
continue with the next procedure.
To check the fuse of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a
b
a
Fuse F1U
b
Fuse F2U
Blown fuse on the main PCB?
Action
Yes
No
and continue with the next procedure.
To check the rectifier voltage of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
1
Turn ON the power of the unit.
2
Measure the voltage on the rectifier voltage check terminals (+ and –) on the
main PCB.
Result:
The measured voltage MUST be approximately 324 V DC.