Split New Perfera R32
ESIE20-11B – 2022.02
7.7.4 To change auto restart ON to OFF
INFORMATION
After power failure, the unit will automatically restart (default setting). It is possible
to switch OFF auto restart. For example: after a long power failure, generators have
to start‑up. As there is limited energy and the air conditioners do NOT have priority,
it is recommended to switch OFF auto restart.
1
Press
,
, and
simultaneously.
2
Press
.
3
Select SU.
4
Press
to confirm.
5
Press
.
6
Select 10.
7
Press
to confirm.
8
Press
.
9
Select 0 (0: auto restart OFF, 1: auto restart ON (factory setting)).
10
Press
to confirm.
7.7.5 To limit the angle of the upper swing flap
For embedded floor standing units, it may be needed to reduce the maximum
angle of the upper swing flap to avoid collission. To do this, perform as described
below.
Prerequisite:
Remove the front panel and the front grille to get access to the
service PCB.
1
Set the DIP switch DS1‑1 to the ON position.
Result:
The maximum angle of the upper swing flap is now reduced.
a
a
Service PCB
ON
ON
OFF
OFF