Class 20~35 unit
a
Nut
b
Compressor
c
Damper
b
a
c
a
c
A
A
Class 42~71 unit
a
Nut
b
Compressor
c
Damper
INFORMATION
The compressor dampers may look different.
7
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
8
Wrap a wet rag around the compressor pipes and any other components near
the compressor and solder the compressor pipes to the refrigerant pipes.