94
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
Is the output voltage on the indoor unit
main PCB correct?
Action
No
Perform a check of the indoor unit main
PCB, see
5
As there are no further check procedures for this component, perform a check
of the indoor unit main PCB to check if the humidity sensor needs to be
replaced. See
106].
After complete check of the indoor unit
main PCB, is the problem solved?
Action
Yes
No further actions required.
No
Replace the humidity sensor, see
4.7.2 Repair procedures
To remove the humidity sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
153].
1
Disconnect the connector from the humidity sensor PCB.
2
Cut the tie strap that fixes the thermistor.
3
Carefully click the complete humidity sensor PCB assembly out of the indoor
unit.
a
b
a
Humidity sensor PCB assembly
b
Tie strap (thermistor fixation)
4
To install the humidity sensor PCB assembly, see
94].
To install the humidity sensor
1
Click the humidity sensor PCB assembly on the indoor unit.