4.8.2 Floor standing indoor units
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the turbo fan assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Remove the swing flap (by clicking it out).
2
Remove the air outlet protection net to create access to the turbo fan.
a
b
c
a
Swing flap
b
Air outlet protection net
c
Turbo fan
3
Slowly rotate the turbo fan using a long‑length tool.
4
If the turbo fan touches the bellmounth, check if the fan motor is correctly
mounted on its base, see
100].
5
Check the state of the turbo fan assembly for damage, deformations and
cracks.
Is the turbo fan assembly damaged?
Action
Yes
Replace the turbo fan assembly, see
No
Perform a mechanical check of the DC
fan motor assembly, see
To perform a mechanical check of the DC fan motor assembly
Prerequisite:
First perform a mechanical check of the propeller fan blade
assembly, see
99].
1
Slowly rotate the turbo fan using a long‑length tool. Check that it rotates
smoothly.
2
Check the friction of the DC fan motor shaft bearing.