ESIE17-08
|
Part 5. Appendix
5.1. Field setting
Page 108
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
5.1.1.3. Sky-Air R32 indoor field settings
Mode No.
First Code No.
Description of Setting
Second Code No.
01
02
03
04
05
10 (20)
0
Filter cleaning sign interval
Long life filter
2,500 hrs. (factory setting)
1,250 hrs.
—
—
—
1
Filter type
Long (factory setting)
Super long
—
—
—
2
Remote controller thermistor
Enabled
Disabled (factory setting)
—
—
—
3
Filter cleaning sign
Display (factory setting)
No display
—
—
—
7 (note 3)
Detection time for NOT presence
30 min (factory setting)
60 min
—
0,,,,0
—
8 (note 4)
Compensation of suction air temperature in heating mode
COMPENSATE
(Temperature [A+2] °C which an air
conditioner controls when the tem-
perature of a remote controller is A
°C) (factory setting)
NO COMPENSATION
(Temperature [A] °C which an air
conditioner controls when the tem-
perature of a remote controller is A
°C)
—
—
—
11 (21)
2
Fan OFF at Thermostat OFF
Normal (factory setting)
OFF
—
—
—
3
Airflow rate setting during heating
Standard (factory setting)
Slightly up
Up
—
—
4
Automatic operation mode control
Available (factory setting)
Prohibition
—
—
—
6 (note 5)
Sensitivity of presence sensor
High
Low
Standard (factory setting)
Sensor does not work
—
11 (22)
0
Option (KRP1B*) output
Compressor (factory setting)
Option
Operation
Malfunction
—
7 (note 5)
Compensation of temperature around human body
Floor sensor does not work
Higher priority on the air tempera-
ture
Standard (factory setting)
Higher priority on the floor tempera-
ture
—
8 (note 5)
Compensation of floor temperature
-4°C
-2°C
±0°C (factory setting)
+2°C
—
12 (22)
3
Fan speed heating thermostat OFF
LL-speed (factory setting)
Set-speed
—
—
—
5
Automatic restart after power failure reset
Disabled
Enabled (factory setting)
—
—
—
6
Fan speed cooling thermostat OFF
LL-speed
Set-speed (factory setting)
—
—
—
13 (23)
0
High air outlet velocity (for high ceiling applications)
Standard (factory setting)
Slightly up
Up
—
—
1
Selection of airflow direction
4-way flow (factory setting)
3-way flow
—
—
—
2
Flap moving in the swing mode
All 4 flaps synchronized
—
Two opposite flaps synchronized
(factory setting)
—
—
4
Airflow range setting
Upper
Normal (factory setting)
Lower
—
—
14 (24)
2
The largest time interval for Dust Collection Sign Display
for "self cleaning decoration panel"
About 1250 hrs (dusty place)
About 2500 hrs (factory setting)
About 5000 hrs (less dusty place)
—
—
4
Display or non-display of green lamp on the selfcleaning
decoration panel
Display both:
- airconditioning operation,
- filter auto cleaning
Non display:
- airconditioning operation,
Display:
- filter auto cleaning
(factory setting)
Display:
- airconditioning operation,
Non display:
- filter auto cleaning
—
—
8
Auto control operation for Filter Auto Cleaning
Auto control operation
Not auto control operation (factory
setting)
—
—
—
9
Filter cleaning time for "selfcleaning decoration panel"
Normal place in terms of dust (Nor-
mal office) (factory setting)
In case of dusty place
—
—
—
15 (25)
5
Individual setting of ventilation
Normal (factory setting)
Individual operation
—
—
—
1b (2b)
14
Wind block (note 6) enable / disable setting
Enable (factory setting)
—
—
—
Disable
I
NFORMATION
1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside parentheses, you can also set by each individual unit. Setting changes however cannot be checked except in the individual mode for those in parentheses. (Even if the setting
are made for the entire group, the display always indicates “01”.)
2. “88” may be displayed to indicate the remote controller is resetting when returning to the normal mode.
3. This function does not work when “SET BACK Function” is set by remote controller.
4. This is the case when the remote sensor (optional kit) is used.
5. This is the case when the sensor option (optional kit) is used.
6. Wind block: one of 4 flaps can be set a block position (block position = closed position).
Wind can not be blocked 100% but mostly blocked without additional parts.