ESIE17-08
|
Part 5. Appendix
5.2. Detailed information setting mode
R32 Sky-Air RZAG-M
15/11/18
|
Version 1.1
Page 111
5.2. Detailed information setting mode
5.2.1. Indoor unit
Not applicable.
5.2.2. Outdoor unit
How to Access & Set the Outdoor Unit Settings (Mode 2)
1. Press and hold the BS1 button for 5 seconds to activate the outdoor unit settings (accessing Mode 2).
2. Press the BS2 button (set) for the required setting.
3. Press the BS3 button (return) once to confirm the setting.
4. Press the BS2 button to set the setting condition.
5. Press the BS3 button once to confirm the setting.
6. Press the BS3 button once to exit the setting.
Outdoor Unit Settings (Mode 2)
No.
Setting item
7 segment display
Setting Condition
7 segment display
SEG1
SEG2
SEG3
SEG1
SEG2
SEG3
2
Power transistor check mode settings
2
0
2
OFF (factory set)
0
ON
1
3
Demand 2 setting out
2
0
3
50%
1
40% (factory set)
2
30%
3
11
TeS lower limit settings
2
1
1
L:0°C
1
M:2°C
2
H:4°C (factory set)
3
HH:6°C
4
28
Refrigerant recovery mode settings
2
2
8
OFF (factory set)
0
ON
1
33
TeS lower settings 2
2
3
3
0 (factory set)
1
6
2
9
3
11
4
13
5
16
6
17
7
TeS lower limit depending on outside temperature
8
34
TcS upper setting
2
3
4
60 (factory set)
1
50
2
47
3
45
4
43
5
TcS upper limit depending on outside temperature
6
55
Drain pan heater ON time after the end of defrosting
2
5
5
1 min (factory set)
1
5 min
2
10 min
3
15 min
4
25 min
5
30 min
6
45 min
7
56
Coefficient A (TeS lower limit depending on outdoor
air temperature)
2
5
6
9 (factory set)
1
11
2
13
3
15
4
57
Coefficient B (TeS lower limit depending on outdoor
air temperature)
2
5
7
2 (factory set)
1
4
2
6
3
8
4
58
Coefficient C (TeS lower limit depending on outdoor
air temperature)
2
5
8
14 (factory set)
1
17
2
20
3
23
4