ESIE17-08
|
Part 2. Troubleshooting
2.1. Error codes check
Page 22
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
2.1.2.3. History of error codes and warnings
As described in above procedure, the latest error or warning codes can also be consulted in Monitor mode:
Setting item 5= latest error
Setting item 6= previous error
Setting item 7= 2 before
For the procedure and the meaning of the different displays, refer to
above.
2.1.2.4. Content of retry
Through the outdoor PCB, the content of retry can be determined.
Here, you can find the errors which are being created before they are being displayed on the user interface.
As described in below procedure, the content of retry can again be consulted in Monitor mode:
Setting item 2= latest retry
Setting item 3= 1 cycle before
Setting item 4= 2 cycles before
To enter "Monitor mode", press the MODE
(BS1) button when in "Setting mode 1".
<Selection of retry or error item>
<Display of RETURN 1>
When the RETURN (BS3) button is pressed,
the LED display for RETURN 1 turns ON.
When SET (BS2) button is pressed, the LED
display for RETURN 2 turns ON.
When SET (BS2) button is pressed, the LED
display for RETURN 3 turns ON.
Press the RETURN (BS3) button to return the
system to the initial state of "Monitor mode".
* Pressing the MODE (BS1) button will bring the
system to the "Setting mode 1".
Press the SET (BS2) button to set the LED
display to retry item.
<Display of RETURN 2>
<Display of RETURN 3>
Check the retry that matches the LED
sequence (see table above).