Troubleshooting by Remote Controller
Troubleshooting R407C PLUS Series Heat Recovery System
155
Outdoor
Unit
J6
9
9
9
Malfunction of thermistor (R2T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
J6
8
7
9
Malfunction of thermistor (R2T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
JA
9
9
9
Malfunction of discharge pipe pressure sensor
JC
9
9
9
Malfunction of suction pipe pressure sensor
JH
8
7
9
Malfunction of oil temperature sensor
—
L0
9
9
9
Failure of inverter system
—
L4
9
9
9
Malfunction of inverter radiating fin temperature rise
L5
9
9
9
Inverter instantaneous over-current
L6
9
9
9
Compressor motor insulation defect, short circuit
—
L8
9
9
9
Inverter thermostat sensor, Compressor overload
L9
9
9
9
Inverter stall prevention, Compressor lock
LA
9
9
9
Malfunction of power unit
—
LC
9
9
9
Malfunction of transmission between inverter and
control PC board
System
P0
9
7
9
Gas depletion (heat build up)
—
P1
9
9
9
Inverter over-ripple protection
P4
9
9
9
Malfunction of inverter radiating fin temperature
sensor
U0
8
7
9
Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
U1
9
9
9
Negative phase / open phase
U2
9
9
9
Power supply insufficient or instantaneous failure
U4
9
9
9
Malfunction of transmission between indoor unit
U5
9
9
9
Malfunction of transmission between remote
controller and indoor unit
U5
7
8
7
Failure of remote controller PC board or setting
during control by remote controller
—
U7
9
9
9
Malfunction of transmission between indoor units
Malfunction of transmission between outdoor units,
malfunction of transmission between outdoor unit and
ice build-up heat unit
—
U7
8
7
9
Malfunction of transmission between outdoor units
(cool/heat unified, low noise)
U8
9
9
7
Malfunction of transmission between master and
slave remote controllers (malfunction of slave remote
controller)
U9
9
9
9
Malfunction of transmission between indoor unit and
outdoor unit in same system
UA
9
9
9
Excessive number of indoor units
UC
8
8
8
Address duplication of central remote controller
UE
9
9
9
Malfunction of transmission between indoor unit and
central remote controller
UF
9
9
9
Refrigerant system not set, incompatible wiring /
piping
UH
9
9
9
Malfunction of system, refrigerant system address
undefined
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Refered
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...