Outline of Control (Outdoor Unit) < Symbols using in this manual >
Si33-105
92
Function R407C PLUS Series Heat Recovery System
Defrosting operation
The defrosting operation provides the following control functions
"
1
Opening degree of indoor unit EV during defrosting operation
• Initial value: 500
• Next indoor unit EV opening degree (200 – 2000) is determined based on (Th7 – Te < 15)
appearing time in previous defrosting operation
0 minute
→
+100
Less than 3 minutes
→
+0
3 minutes or more
→
–100
"
2 Refer to p.84 .
(V0807)
PI control
All indoor EV 1000pls (50 sec)
→
0pls (10 sec)
→
End of preparation operation to 4-way valve
changeover
→
50pls (10 sec
H
10)
Control SH
according to
H
4
EV1, EV2 (main unit) = 0pls, EV3 (sub unit) = 2000pls
Normal control
PI control
52Hz+OFF
+(OFF)
29Hz+OFF
+(OFF)
[B]
[A]
[E]
H
9
H
3
H
2
H
2
H
2
(
H
10)
(
H
1)
SC
control
SH
control
SC control
Normal control
Normal control
Instruction
cancel
Instruction
cancel
200pls
200pls
(
H
10)
(
H
7)
(
H
8)
(
H
10)
(
H
1)
INV
SVP
Outdoor EV
Indoor EV
(Heating unit)
Indoor EV
(Cooling unit)
Outdoor fan
20S1
20S2
20RL
20RH
20RT
Defrost
preparation flag
Defrost
IN
BS unit
changeover
Defrost
OUT
1 min
1 min
Oil return, defrost
preparing signal
output
10 sec
Defrost
Discharge
Suction
Accumulator
discharge
operation
10 sec 10 sec 40 sec
30 sec
(7 min)
2 min
50 sec
20S3
SVRVG
BS unit
solenoid valve
50 sec 10 sec
2000pls only for sub unit side EV after 1 min from preparation
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...