Outline of Control (Indoor Unit)
Si33-105
100
Function R407C PLUS Series Heat Recovery System
4.3
Thermostat Sensor in Remote Controller
Temperature is controlled by both the thermostat sensor in remote controller and air suction
thermostat in the indoor unit. (This is however limited to when the field setting for the thermostat
sensor in remote controller is set to “Use.” )
Cooling
If there is a significant difference in the preset temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
remote controller near the position of the user when the suction temperature is near the preset
temperature.
!
Ex: When cooling
Assuming the preset temperature in the figure above is 24°C, and the suction
temperature has changed from 18°C to 30°C (A
→
F):
(This example also assumes there are several other air conditioners, the VRV system is off, and
that temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18°C to 23°C (A
→
C).
Remote controller thermostat sensor is used for temperatures from 23°C to 27°C (C
→
E).
Body thermostat sensor is used for temperatures from 27°C to 30°C (E
→
F).
And, assuming suction temperature has changed from 30°C to 18°C (F
→
A):
Body thermostat sensor is used for temperatures from 30°C to 25°C (F
→
D).
Remote controller thermostat sensor is used for temperatures from 25°C to 21°C (D
→
B).
Body thermostat sensor is used for temperatures from 21°C to 18°C (B
→
A).
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...