3.13 Outdoor Unit:
Actuation of Safety Device
Remote
Controller
Display
E0
Supposed
Causes
!
Actuation of outdoor unit safety device
!
Defect of outdoor unit PC board
!
Instantaneous power failure
Troubleshooting
"
1: Actuation of magnet switch OC
Defect of compressor
Power supply insufficient
Defect of magnet switch, etc.
"
2: Actuation of fan motor safety thermostat
Defect of fan motor
Defect of capacitor, etc.
(VF040)
Connector
or terminal is
connected to X8A, X9A
and X80A of the outdoor
unit PC board
(A1P).
Contacts
F2C (X1S - X2S) are
open.
Connect the connector or terminal
and turn on again.
Actuation of magnet switch
OC for standard compressor.
H
1
Actuation of fan motor safety
thermostat.
H
2
YES
NO
NO
YES
Contact
Q1M (X8A) or Q2M (X9A)
is open.
NO
YES
Operation
is normal when turned
on again by remote
controller.
YES
NO
Replace outdoor unit PC board
A1P.
There was an instantaneous
power failure or a past safety
device actuated. Re-check
refrigerant system.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...