Si33-105
Troubleshooting (OP: Schedule Timer)
Troubleshooting R407C PLUS Series Heat Recovery System
209
7. Troubleshooting (OP: Schedule Timer)
7.1
Malfunction of Transmission Between Central Remote
Controller and Indoor Unit
Remote
Controller
Display
UE
Supposed
Causes
!
Malfunction of transmission between central remote controller and indoor unit
!
Disconnection of connector for setting master controller (or individual/combined switching
connector)
!
Defect of schedule timer PC board
!
Defect of indoor unit PC board
Troubleshooting
(VF075)
Is
the power supply
turned on for indoor
units displaying
malfunction?
Is
transmission wiring
disconnected or wired
incorrectly?
Is
the transmission
wiring with the master
controller disconnected or
wired incorrectly?
Is
the master controller's
connector for setting master
controller
disconnected?
Set the group No. correctly.
Replace indoor unit PC board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector
correctly.
Replace the central PC board.
Reset power supply
simultaneously for all optional
controllers for centralized
control.
NO
YES
NO
YES
YES
NO
NO
Turn indoor unit's power
supply.
YES
NO
NO
YES
YES
YES
NO
Has
an indoor unit
once connected been
remove or its address
changed?
Is the group
No. of malfunctioning
indoor units set?
Is
transmission with all
indoor units
malfunctioning?
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...