Si33-105
Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting R407C PLUS Series Heat Recovery System
215
8.2
Display “Under Host Computer Integrate Control” Blinks
(Repeats Single Blink)
Remote
Controller
Display
“under host computer integrated control” (Repeats single blink)
Supposed
Causes
!
Address duplication of central remote controller
!
Improper combination of optional controllers for centralized control
!
Connection of more than one master controller
!
Malfunction of transmission between optional controllers for centralized control
!
Defect of PC board of optional controllers for centralized control
Troubleshooting
(VF080)
Is
the reset switch
of all optional controllers for
centralized control set to
"normal"?
Is
transmission wiring
disconnected or wired
incorrectly?
Correct the setting of the
unified ON / OFF controller's
switch for setting each
address and reset the power
supply of the unified ON /
OFF controller.
Refer to failure diagnosis for
central remote controller or
schedule timer.
NO
YES
YES
NO
NO
Fix the wiring correctly.
Set reset switch to "normal".
NO
NO
YES
YES
YES
Is
the power supply
turned on for all optional
controllers for centralized
control?
Reset power supply
simultaneously for all optional
controllers for centralized
control.
NO
YES
Has a once
connected optional
controller for centralized
control been disconnected
or itsaddress
changed?
Is
the central remote
controller or schedule timer
displaying a
malfunction?
Is
a central remote
controller or schedule timer
connected?
Turn on power supply for all
optional controllers for
centralized control.
NO
YES
NO
Is
the setting of the
unified ON / OFF controller's
switch for setting each
address
duplicated?
Are
two or more unified
ON / OFF controllers
connected?
YES
2A
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...