Outline of Control (Outdoor Unit) < Symbols using in this manual >
Si33-105
70
Function R407C PLUS Series Heat Recovery System
3.4.4
BS Unit Basic Operation
Contents
Instructs ON/OFF operation of BS unit solenoid valve from outdoor unit depending on the
operating state of indoor unit. However, regarding non-ordinary operation of startup control,
defrosting, oil return, and equalizing control, BS unit solenoid valve is switched under the
individual control. This section describes only the basic operation by indoor unit operation
mode.
1. During compressor operation
"
1. The solenoid valve is turned ON only when in simultaneous cooling/heating mode
"
2. Remote controller setting judgement is not conducted when operation button is in OFF.
(Returns to operation of stopping unit in the previous mode)
2. During compressor stop
Regardless of the indoor unit temperature control and operating state, turns off all solenoid
valves.
Indoor unit
temperature
control mode
Indoor unit
operating
condition
Suction solenoid
valve
(20RL)
Discharge
solenoid valve
(20RH)
Bypass solenoid
valve
(20RT)
Cooling
Thermostat ON
ON
OFF
OFF
Thermostat OFF
OFF
Stop
Heating
Thermostat ON
OFF
ON
"
1
Thermostat OFF
OFF
Stop
Fan
OFF
OFF
OFF
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...