Si33-105
Outline of Control (Outdoor Unit) < Symbols using in this manual >
Function R407C PLUS Series Heat Recovery System
83
3.5.8
Drooping due to Outdoor Temperature
Purpose
!
When the outdoor temperature is high, the temperature inside inverter box does not reach to
the reference value. Therefore, conducts forced drooling.
Contents
!
Provide upper limit compressor operation frequency based on the following conditions.
3.5.9 Demand Control
Forcibly reduces the outdoor unit capacity based on an external contact input (demand input) to
decrease power consumption. The following three types of demand control are provided.
!
Other protection control functions have precedence over the above operations.
"
Optional PCB is required for this control. (DTA104A61, 62)
(V2583)
Normal operation
Set the upper limit compressor operation
frequency to the frequency shown below.
20HP model or lower (in 2 compressor system)
= 87Hz + ON
24HP model or higher (in 3 compressor system)
= 87Hz + ON + ON
Ta
≥
39˚C
Inv_A
≥
28A
OR
Ta<37˚C
Inv_A<25A
&
Note) Inv_A : Current sent from inverter
Compressor upper-limit
frequency
Capacity reduction guideline
Demand control 1
A
Reduces power consumption to approx. 70%
Demand control 2
B
Reduces power consumption to approx. 40%
Demand control 3
All compressors in stop mode
Forced thermostat OFF
Model
Upper-limit frequency (A)
Model
Upper-limit frequency(B)
INV
STD1
STD2
INV
STD1
STD2
RSXYP16KJ
46Hz
+ON
—
RSXYP16KJ
52Hz
+OFF
—
RSXYP18KJ
52Hz
+ON
—
RSXYP18KJ
62Hz
+OFF
—
RSXYP20KJ
52Hz
+ON
—
RSXYP20KJ
62Hz
+OFF
—
RSXYP24KJ
87Hz
+ON
+OFF
RSXYP24KJ
79Hz
+OFF
+OFF
RSXYP26KJ
87Hz
+ON
+OFF
RSXYP26KJ
79Hz
+OFF
+OFF
RSXYP28KJ
33Hz
+ON
+ON
RSXYP28KJ
33Hz
+ON
+OFF
RSXYP30KJ
33Hz
+ON
+ON
RSXYP30KJ
33Hz
+ON
+OFF
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...