6 Technical data

Installation manual

9

8T7V1B*
VRV IV heat exchanger unit for indoor installation
4P408444-1B – 2016.04

D

B

C

b2

b3

c1

c2

b1

a

A

A

Central user interface (etc...)

B

Compressor unit

C

Indoor unit

D

Heat exchanger unit

a

Main line. The main line is the line to which the
transmission wiring of the heat exchanger unit is
connected.

b1, b2, b3

Branch lines

c1, c2

No branch is allowed after branch

5.4.2

Guidelines when connecting the electrical
wiring

Tightening torques

Wiring

Screw size

Tightening torque

(N•m)

Power supply wiring

(power
shielded ground)

M5

2.0~3.0

Transmission wiring

M3.5

0.8~0.97

5.4.3

To connect the electrical wiring on the
heat exchanger unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

1

Remove the service cover.

2

Connect the transmission wiring as follows:

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

b

X2M

X2M

X2M

X1M (A1P)

RKXYQ5

RDXYQ5

TO OUT/D

TO IN/D

F1 F2

F1 F2

a1

a2

a2

a

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

b

a

RKXYQ8

RDXYQ8

TO OUT/D

TO IN/D

F1 F2

F1 F2

8 HP

5  HP

a

Sh shielded cable (2 wires) (no polarity)

a1, a2

Connection of shield to earth

b

Terminal board (field supply)

WARNING

Shielded cable.

 Using shielded cable for the transmission

wiring is mandatory for 5 HP, and optional for 8 HP.

X2M

F1F2

F1F2

a1

X1M

X1M (A1P)

5 HP

8 HP

X2M

a2

F1

F2

X2M

a2

F1

F2

RKXYQ5

RDXYQ5

RKXYQ8

RDXYQ8

a1, a2

 Earth (use the screw delivered as accessory)

When using shielded cable:

▪ In case of 5 HP (

a1

 and 

a2

): Connect the shield to the

earth  of  the  compressor  unit  and  the  heat  exchanger
unit.

▪ In  case  of  8  HP  (only 

a2

):  Connect  the  shield  only  to

the earth of the heat exchanger unit.

3

Connect the power supply as follows:

1~ 50 Hz

220-240 V

X1M

a

b

c

a

Earth leakage circuit breaker

b

Fuse

c

Power supply cable

4

Route  the  wiring  through  the  frame,  and  fix  the  cables  (power
supply and transmission wiring) with cable ties.

A1P

X1M

X2M

b

a

c

c

a

Transmission wiring

b

Power supply

c

Cable tie

6

Technical data

Latest information can be found in the technical engineering data.

Summary of Contents for RDXYQ8T7V1B

Page 1: ...Installation manual VRV IV heat exchanger unit for indoor installation English Installation manual VRV IV heat exchanger unit for indoor installation RDXYQ5T7V1B RDXYQ8T7V1B...

Page 2: ...iten befinden sich entsprechend Artikel 1 2f des PED au erhalb der Reichweite Risikoart H Siehe auch n chste Seite tel que d fini dans A et valu positivement par B conform ment au Certificat C tel que...

Page 3: ...stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Minim...

Page 4: ...arget audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Documenta...

Page 5: ...ing units and options 3 3 1 Possible options for the compressor unit and heat exchanger unit For more possible options see the installer and user reference guide Drain pan heater EKDPH1RDX When Instal...

Page 6: ...unit and all indoor units and between compressor unit and heat exchanger unit 600 m If the total transmission wiring exceeds these limits it may result in communication error 5 Installation 5 1 Openin...

Page 7: ...Discharge ducting 5 2 3 Guidelines when installing the drain piping Make sure condensation water can be evacuated properly This involves General guidelines Connecting the drain piping to the heat exc...

Page 8: ...NG 5 3 1 To connect the refrigerant piping to the heat exchanger unit 1 Remove the cover 2 Remove the 2 insulation pieces 3 Put a wet cloth in front of the EPS to protect the drain pan 4 Braze the liq...

Page 9: ...F2 F1 F2 F1 F2 b X2M X2M X2M X1M A1P RKXYQ5 RDXYQ5 TO OUT D TO IN D F1 F2 F1 F2 a1 a2 a2 a F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 b a RKXYQ8 RDXYQ8 TO OUT D TO IN D F1 F2 F1 F2 8 HP 5...

Page 10: ...iring depending on model PCB Legend for wiring diagram 5 8 HP A1P Printed circuit board main A2P Printed circuit board adapter C1 Capacitor A1P E1H Drain pan heater optional F1U Fuse F 1 A 250 V optio...

Page 11: ......

Page 12: ...4P408444 1 B 0000000 4P408444 1B 2016 04 Copyright 2015 Daikin...

Reviews: