6 Technical data
Installation manual
9
8T7V1B*
VRV IV heat exchanger unit for indoor installation
4P408444-1B – 2016.04
D
B
C
b2
b3
c1
c2
b1
a
A
A
Central user interface (etc...)
B
Compressor unit
C
Indoor unit
D
Heat exchanger unit
a
Main line. The main line is the line to which the
transmission wiring of the heat exchanger unit is
connected.
b1, b2, b3
Branch lines
c1, c2
No branch is allowed after branch
5.4.2
Guidelines when connecting the electrical
wiring
Tightening torques
Wiring
Screw size
Tightening torque
(N•m)
Power supply wiring
(power
shielded ground)
M5
2.0~3.0
Transmission wiring
M3.5
0.8~0.97
5.4.3
To connect the electrical wiring on the
heat exchanger unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1
Remove the service cover.
2
Connect the transmission wiring as follows:
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
b
X2M
X2M
X2M
X1M (A1P)
RKXYQ5
RDXYQ5
TO OUT/D
TO IN/D
F1 F2
F1 F2
a1
a2
a2
a
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
b
a
RKXYQ8
RDXYQ8
TO OUT/D
TO IN/D
F1 F2
F1 F2
8 HP
5 HP
a
Sh shielded cable (2 wires) (no polarity)
a1, a2
Connection of shield to earth
b
Terminal board (field supply)
WARNING
Shielded cable.
Using shielded cable for the transmission
wiring is mandatory for 5 HP, and optional for 8 HP.
X2M
F1F2
F1F2
a1
X1M
X1M (A1P)
5 HP
8 HP
X2M
a2
F1
F2
X2M
a2
F1
F2
RKXYQ5
RDXYQ5
RKXYQ8
RDXYQ8
a1, a2
Earth (use the screw delivered as accessory)
When using shielded cable:
▪ In case of 5 HP (
a1
and
a2
): Connect the shield to the
earth of the compressor unit and the heat exchanger
unit.
▪ In case of 8 HP (only
a2
): Connect the shield only to
the earth of the heat exchanger unit.
3
Connect the power supply as follows:
1~ 50 Hz
220-240 V
X1M
a
b
c
a
Earth leakage circuit breaker
b
Fuse
c
Power supply cable
4
Route the wiring through the frame, and fix the cables (power
supply and transmission wiring) with cable ties.
A1P
X1M
X2M
b
a
c
c
a
Transmission wiring
b
Power supply
c
Cable tie
6
Technical data
Latest information can be found in the technical engineering data.