20
|
Configuration
Installer and user reference guide
136
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
[2‑82]
Heating comfort setting.
This setting is used in conjunction with setting [2‑9].
[2‑82]
Heating comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings, see
"20.3 Energy saving and optimum operation"
[2‑85]
Automatic leak detection interval time.
This setting is used in conjunction with setting [2‑86].
[2‑85]
Time between automatic leak detection executions
(days)
0 (default)
365
1
180
2
90
3
60
4
30
5
7
6
1
[2‑86]
Automatic leak detection activation.
When you want to use the automatic leak detection function you have to activate
this setting. By activating setting [2‑86], the automatic leak detection will be
executed depending on the defined value setting. The timing for the next
automatic refrigerant leak detection is subject to setting [2‑85]. The automatic leak
detection will be executed in [2‑85] days.
Each time when the automatic leak detection function was executed the system
will stay idle until it is restarted by manual thermo ON request or by next
scheduled action.
[2‑86]
Description
0 (default)
No leak detection planned.
1
Leak detection planned once in [2‑85] days.
2
Leak detection planned every [2‑85] days.