24
|
Troubleshooting
Installer and user reference guide
160
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
Main code
Sub code
Cause
Solution
Master
Slave 1
Slave 2
—
Unit is not prepared to execute
leak detection operation
Refer to requirements to be
able to execute leak detection
operation.
—
Indoor unit is out of
temperature range for leak
detection operation
Retry when ambient conditions
are satisfied.
—
Outdoor unit is out of
temperature range for leak
detection operation
Retry when ambient conditions
are satisfied.
—
Too low pressure was noticed
during leak detection operation
Restart leak detection
operation.
—
Indicates an indoor unit which
is not compatible with leak
detection functionality is
installed (e.g. Hydrobox, …)
Refer to requirements to be
able to execute leak detection
operation.