17
|
Unit installation
Installer and user reference guide
61
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
17 Unit installation
In this chapter
17.1 Preparing the installation site
17.1.1 Installation site requirements of the outdoor unit
▪
Provide sufficient space around the unit for servicing and air circulation.
▪
Make sure the installation site withstands the weight and vibration of the unit.
▪
Make sure the area is well ventilated. Do NOT block any ventilation openings.
▪
Make sure the unit is level.
▪
Select a place where rain can be avoided as much as possible.
▪
Select the location of the unit in such a way that the sound generated by the unit
does not disturb anyone, and the location is selected according the applicable
legislation.
Do NOT install the unit in the following places:
▪
In potentially explosive atmospheres.
▪
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of
the equipment.
▪
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
▪
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
▪
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
NOTICE
This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
Summary of Contents for REMQ5U7Y1B
Page 173: ......
Page 174: ......
Page 175: ......
Page 176: ...4P561154 1A 2020 10 Copyright 2018 Daikin Verantwortung für Energie und Umwelt ...