18
|
Piping installation
Installer and user reference guide
76
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
If
Then
The outdoor unit is positioned higher
than the indoor units
▪
Minimum connection ratio: 80%
▪
Size up the liquid piping (refer to
71] for more
information)
▪
Activate the outdoor unit setting.
Refer to the service manual for more
information.
The outdoor unit is positioned lower
than the indoor units
▪
Minimum connection ratio varies
according to the height difference
between outdoor and indoor units:
-
40~60 m: 80%
-
60~65 m: 90%
-
65~80 m: 100%
-
80~90 m: 110%
▪
Size up the liquid piping (refer to
71] for more
information)
▪
Activate the outdoor unit setting.
Refer to the service manual for more
information.
▪
No technical cooling
18.1.6 Single outdoor units and standard multi-outdoor-unit combinations >20 HP
Connection with only VRV DX indoor units
H3
1
5
H1
H2
3
2
4
a
b
b
c
d
e
e
a
Outdoor unit
b
VRV DX indoor unit
c
Multi BS unit
d
BS unit
e
VRV DX indoor unit