18
|
Piping installation
Installer and user reference guide
79
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
Pipe
Maximum length (actual/equivalent)
In case of a multi-outdoor setup:
longest pipe from the outdoor unit to
the last multi-outdoor piping branch (4)
10 m/13 m
Total pipe length
1000 m/—
(a) If the equivalent piping length is more than 90 m, size up the main liquid piping
18.1.7 Standard multi-outdoor-unit combinations ≤20 HP and free multi-outdoor-unit
combinations
Connection with only VRV DX indoor units
H3
1
5
H1
H2
3
2
4
a
b
b
c
d
e
e
a
Outdoor unit
b
VRV DX indoor unit
c
Multi BS unit
d
BS unit
e
VRV DX indoor unit
Pipe
Maximum length (actual/equivalent)
Longest pipe from the outdoor unit or
the last multi-outdoor piping branch
(1+2, 1+3, 1+5)
135 m/160 m
(a)
Longest pipe after the first branch (2, 3,
5)
40 m/—
(b)
In case of a multi-outdoor setup:
longest pipe from the outdoor unit to
the last multi-outdoor piping branch (4)
10 m/13 m
Total pipe length
500 m/—
(a) If the equivalent piping length is more than 90 m, size up the main liquid piping