• Outdoor Units • VRV HEAT RECOVERY • REYHQ16-24P
1
9
• VRV Systems • Outdoor Units
33
9
Installation
9 - 1
Service space
REYHQ12P8
3D051451M
N
OTES
1
Height of walls in case of Patterns 1 and 2
Front: 1500mm
Suction side: 500mm
Side: Height unrestricted.
Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
when the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in
all outdoor unit, take the suction side space more broadly than the space to be shown in this drawing.
2
If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in
the figure on the right.
3
When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available
always bearing in mind the need to leave enough space for a person to pass between units and wall and for the air circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4
The units should be installed to leave insufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
For single unit installation
For installation in rows
For centralized group layout
<Pattern 1>
<Pattern 1>
<Pattern 1>
<Pattern 2>
<Pattern 2>
<Pattern 3>
<Pattern 2>
<Pattern 3>
10 or more
10 or more
20 or more
10 or more
10 or more
20 or more
500 or more
500 or more
500 or more
500 or more
200 or more
200 or more
300 or more
300 or more
300 or more
10 or more
10 or more
10 or more
10 or more
20 or more
20 or more
<Front>
500 or more
600 or more
300 or more
10 or more
10 or more
20 or more
<Front>
500 or more
300 or more
20 or more
10 or more
10 or more
<Front>
50 or more
50 or more
100 or more
<Front>
500 or more
<Front>
50 or more
50 or more
50 or more
50 or more
50 or more
50 or more
500 or more
500 or more
<Front>
<Front>
100 or more
100 or more
100 or more
100 or more
100 or more
<Unit:mm>
<Fr
ont>
<S
uction side>
300 or more
<Front>
Wall height unrestricted
<Front>
400 or more
400 or more
Wall height unrestricted
100 or more
100 or more
<Front>
<Front>
50 or more
50 or more
100 or more
100 or more
50 or more
50 or more
<Front>
<Front>
<Front>
100 or more