• Outdoor Unit • REYQ-T
2
• VRV Systems • REYQ-T
10
2
Specifications
Notes
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for
standard efficiency series
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard
efficiency series
If the indoor temperature is below 20°C before the start of the leak detection function, the unit will first heat the room to reach at least 20°C
Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% \<= CR
\<= 130%)
Technical cooling setting, refer to the installation manual for more information
Field setting
Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
Sound values are measured in a semi-anechoic room.
For detailed contents of standard accessories see Installation manual.
REMQ5 unit cannot be used as standalone unit.
Refer to refrigerant pipe selection or installation manual
RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always
≤
max. running current.
MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
TOCA means the total value of each OC set.
FLA: nominal running current fan
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected
only to a supply with Zsys
≤
Zmax, respectively Ssc
≥
minimum Ssc value.
EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment
with rated
≤
75A
EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current
\> 16A and
≤
75A per phase
Short-circuit power
system impedance
Contains fluorinated greenhouse gases
Soundpressure and soundpower for multi units can be calculated, following below instructions.
Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account.
Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
2-9 Technical Specifications
REMQ5T
Dimensions
Unit
Height
mm
1,685
Width
mm
930
Depth
mm
765
Packed unit
Height
mm
1,820
Width
mm
1,000
Depth
mm
835
Weight
Unit
kg
210
Packed unit
kg
226
Packing
Material
Carton
Weight
kg
2.00
Packing 2
Material
Wood
Weight
kg
17.00